www.DaikinApplied.com 65
IM 817-7
WARNING
To avoid electrical shock, personal injury or death, be sure that field
wiring complies with local and national fire, safety, and electrical
codes, and voltage to the system is within the limits shown in the
job-specific drawings and unit electrical data plate(s). Power supply
to unit must be disconnected when making field connections.
Rigorously adhere to field wiring procedures regarding proper lockout
and tagout of components.
Electric Heating
Table 42: Standard Motor Electric Heat Capacities, Amps, Wire Sizing, and Over Current Protection
Unit Type
AVS AVV
AVR
AVV AVR AVS AVV
AVR
AVV AVR AVS AVV
AVR
AVV AVR AVS AVV
AVR
AVV AVR
Number of Electric Elements
3
6
3
6
3
6
3
6
KW
6
12
8
16
10
20
12
24
MBH
20.48
40.96
27.30
54.61
34.13
68.26
40.96
81.91
Final Air Temp F (70 F entering air temp)
95.20
120.30
95.20
120.30
95.20
120.30
95.20
120.30
Air Temperature Rise
25.20
50.30
25.20
50.30
25.20
50.30
25.20
50.30
208-60-1
Electric Heating Amperes
28.80
57.70
38.50
76.90
48.10
96.20
57.70
115.40
Unit Minimum Circuit Ampacity
39.10
75.23
51.23
99.23
63.23
123.35
75.23
147.35
Maximum Fuse Size or Circuit Breaker Amps
40
80
55
100
70
130
80
150
230-60-1
Electric Heating Amperes
25.04
50.09
33.18
66.37
41.63
83.27
50.09
100.17
Unit Minimum Circuit Ampacity
34.40
65.71
44.58
86.06
55.14
107.19
65.71
128.32
Maximum Fuse Size or Circuit Breaker Amps
35
70
45
90
60
110
70
130
265-60-1
Electric Heating Amperes
21.74
43.59
28.85
57.70
36.17
72.33
43.59
87.07
Unit Minimum Circuit Ampacity
30.28
57.59
39.16
75.22
48.31
93.52
57.59
111.94
Maximum Fuse Size or Circuit Breaker Amps
35
60
40
80
50
100
60
120
208-60-3
Electric Heating Amperes
16.70
33.30
22.20
44.40
27.80
55.50
33.30
66.60
Unit Minimum Circuit Ampacity
23.98
44.73
30.85
58.60
37.85
72.48
44.73
86.35
Maximum Fuse Size or Circuit Breaker Amps
25
45
35
60
40
80
45
90
230-60-3
Electric Heating Amperes
14.50
28.90
19.20
38.30
24.00
48.10
28.90
57.81
Unit Minimum Circuit Ampacity
21.23
39.23
27.10
50.97
33.10
63.23
39.23
75.36
Maximum Fuse Size or Circuit Breaker Amps
25
40
30
55
35
70
40
80
460-60-3
Electric Heating Amperes
7.20
14.50
9.60
19.20
12.00
24.00
14.50
28.90
Unit Minimum Circuit Ampacity
12.10
21.23
15.10
27.10
18.10
33.10
21.23
39.23
Maximum Fuse Size or Circuit Breaker Amps
15
25
20
30
20
35
25
40
Notes:
1. Unit wire sizing should be determined in accordance with NEC and local codes.
2. Amps at unit voltage, 60Hz, single phase
3. External static pressure ranges must be strictly adhered to.