Basic Control
SiUS341802E
53
Functions and Control
5.6
Step Control of Outdoor Fans
Used to control the revolutions of outdoor fans in the steps listed in table below, according to condition changes.
Step No.
Standard (default)
Cooling
Heating
M1F
M2F
M1F
M2F
0
0
0
0
0
1
281
0
281
0
2
290
0
290
0
3
300
0
300
0
4
310
0
310
0
5
329
0
329
0
6
343
0
343
0
7
357
0
357
0
8
371
0
371
0
9
386
0
386
0
10
402
0
402
0
11
419
0
419
0
12
436
0
436
0
13
453
0
453
0
14
472
0
472
0
15
491
0
491
0
16
511
0
511
0
17
532
0
532
0
18
554
0
554
0
19
576
0
576
0
20
287
317
287
317
21
300
330
300
330
22
314
344
314
344
23
320
350
320
350
24
332
362
332
362
25
345
375
345
375
26
358
388
358
388
27
372
402
372
402
28
386
416
386
416
29
401
431
401
431
30
417
447
417
447
31
434
464
434
464
32
451
481
451
481
33
470
500
470
500
34
489
519
489
519
35
509
539
509
539
36
531
561
531
561
37
553
583
553
583
38
577
607
577
607
39
601
631
601
631
40
627
657
627
657
41
655
685
655
685
42
683
713
683
713
43
713
743
713
743
44
745
775
745
775
45
778
808
778
808
46
813
843
813
843
47
849
879
849
879
48
888
918
888
918
49
958
928
958
928
50
1040
930
1040
930
51
1131
1021
1131
1021
52
1232
1132
1232
1132
53
1360
1180
1360
1180
RXLQ72/96TA, RXYQ72TA cooling upper limit
RXLQ120TA, RXYQ96/120TA cooling upper limit
RXYQ144/168TA cooling,
All models heating upper limit
Step X
Cooling
Heating
RXLQ72TA
49
51
RXLQ96TA
51
51
RXLQ120TA
52
52
RXYQ72TA
49
51
RXYQ96TA
51
52
RXYQ120TA
52
52
RXYQ144TA
53
53
RXYQ168TA
53
53
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...