11
|
Configuration
Installer reference guide
166
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
Description
[3.6]
[0-04]
[0-05]
[0-06]
[0-07]
Set weather-dependent cooling:
Note:
There are 2 methods to set the weather
145]. Both curve
types require 4 field settings to be configured
according to the figure below.
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪
T
t
:
Target
leaving
water
temperature
(additional zone)
▪
T
a
: Outdoor temperature
▪
[0-07]: Low outdoor ambient temperature.
10°C~25°C
▪
[0-06]: High outdoor ambient temperature.
25°C~43°C
▪
[0-05]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be higher than [0‑04]
as for low outdoor temperatures less cold
water is required.
▪
[0-04]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be lower than [0‑05] as
for high outdoor temperatures colder water is
required.
Emitter type
For more information about
Emitter type
#
Code
Description
[3.7]
[2‑0D]
Emitter type
:
▪
0:
Underfloor heating
▪
1:
Fancoil unit
▪
2:
Radiator
The setting of the emitter type has an influence on the space heating setpoint
range and the target delta T in heating as follows: