9
|
Electrical installation
Installer reference guide
116
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
X1
X2
X1
X2
X2M
A4P
a
a
Installation of EKRP1HBAA is required.
3
Fix the cable with cable ties to the cable tie mountings.
9.2.12 To connect the power consumption digital inputs
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage
supplied by PCB)
[9.9]
Power consumption control
.
1
2
Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.
S6S (DI4)
A8P.1
A8P.2
A8P.3
A8P.4
A8P.5
S7S (DI3)
S8S (DI2)
S9S (DI1)
X801M
3 4 5
2
1
A8P
a
a
Installation of EKRP1AHTA is required.
3
Fix the cable with cable ties to the cable tie mountings.