Installation manual

 

4

 

EKHWE150~3 E300A3Z2

 

Domestic hot water tank for air to water heat pump system

 

4PW43396-1D

 

4

 

Install the 3-way valve body in the pipework.

Make sure the shaft will be positioned in such a way that the
motor can be mounted and replaced.

Put the sleeve on the valve and turn the valve to the middle
position of the scale plate.
Check that the valve is positioned as in the figure below. It
should be blocking the outlet connection to the domestic hot
water for 50% and the outlet connection to the room heating
also for 50%.

 

5

 

When installing in accordance with 

figure A

 or 

figure D

, open the

valve motor cover by loosening the screw and change the
jumper so as to change the rotation direction of the valve.

By default the jumper is factory set to apply for installation in
accordance with 

figure B

 and 

figure C

.

 

6

 

Push the motor on the motor sleeve. 

Make sure not to rotate the sleeve during this action, so as to
maintain the valve position as set during step 

4

.

 

7

8

 

Put the scale on the valve as shown below.

 

9

 

Make sure to firmly fix the power supply cord onto the 3-way
valve body with a field supplied cable tie like in illustration below.

 

10

 

Perform the wiring in the indoor unit in accordance with the
following figure:

Refer also to the drawing on 

page 6

.

 

Connecting the water circuits

1

Connect the water inlet and water outlet from the heat
exchanger. 

2

Connect the hot and cold water supply tubes.

3

Connect the pressure relief valve (field supply, opening pressure
maximum 10 bar).

Field wiring

Power circuit and cable requirements

For cable requirements and specifications, refer to "Field wiring" in
the indoor unit installation manual supplied with the EKHBH/X unit.

Installation in accordance with 

figure A

 and 

figure B

Installation in accordance with 

figure C

 and 

figure D

If the valve is not positioned in this way before mounting
the motor, the valve will give way to both domestic water
and room heating during operation.

Installation in accordance with 

figure A

 and 

figure D

Installation in accordance with 

figure B

 and 

figure C

Rotation direction of the valve

Domestic hot 

water tank

Room heating

Room heating

Domestic hot 

water tank

Installation in accordance with

figure B and figure C

Installation in accordance with

figure A and figure D

L

N

Y

DIR

2P

8

9

10

3-way valve

BRN

BLU

BLK

L

N

Y

Make sure to use galvanic couplings for the connection.

If a discharge pipe is connected to the pressure relief
device it must be installed in a continuously downward
direction and in a frost-free environment. It must be left
open to the atmosphere.

A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local and national legislation.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance
with the wiring diagram supplied with the unit and the
instructions given below.

The domestic hot water tank must be earthed via the
indoor unit.

Be sure to use a dedicated power circuit. Never use a
power circuit shared by another appliance.

Use one and same dedicated power supply for the
outdoor unit, indoor unit, backup heater and domestic
hot water tank.

NOTE

Select the power cable in accordance with relevant
local and national regulations.

Содержание Altherma EKHWE150A3V3

Страница 1: ...INSTALLATION MANUAL EKHWE150A3V3 EKHWET150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 Domestic hot water tank for air to water heat pump system ...

Страница 2: ... 30 30 50 700 300 440 500 4 5 30 30 700 400 705 220 255 280 35 115 775 1150 13 21 355 440 50 EKHWE150 300 EKHWET150 D1 1150 775 280 255 35 545 1525 925 280 410 35 545 1525 851 210 410 27 660 H1 H2 H3 H4 H5 Ø D1 150 200 EKHWE 300 A A A A 16 16 16 400 400 0 400 77 111 38 67 44 2 1 3 ...

Страница 3: ... EKHWET150A3V3 EKHWE200A3V3 EKHWE200A3Z2 EKHWE300A3V3 EKHWE300A3Z2 Domestic hot water tank for air to water heat pump system Installation manual READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQU...

Страница 4: ...stic hot water quality must be according to EN directive 98 83 EC A drain device should be installed on the cold water connection on the domestic hot water tank For safety reasons it is not allowed to add ethylene glycol to the water circuit Adding ethylene glycol might lead to contamination of the domestic water if a leakage would occur in the heat exchanger coil It is important that the storage ...

Страница 5: ...d back siphonage it is advised to install a non return valve on the water inlet of the domestic hot water tank in accordance with local and national regulations Installing the domestic hot water tank 1 Check if all domestic hot water tank accessories see Accessories on page 1 are enclosed 2 When floor mounting place the domestic hot water tank on a level surface If required adjust the legs at the ...

Страница 6: ...tions refer to Field wiring in the indoor unit installation manual supplied with the EKHBH X unit Installation in accordance with figure A and figure B Installation in accordance with figure C and figure D If the valve is not positioned in this way before mounting the motor the valve will give way to both domestic water and room heating during operation Installation in accordance with figure A and...

Страница 7: ...ector connected to the contactor K3M in the socket X13A on the PCB 5 Plug the thermistor cable connector in the socket X9A on the PCB 6 Connect the prewired earth wires of the terminal block X3M and X4M to the earthing screw 7 Connect the booster heater power supply and thermal protection cable field supply to terminal X4M earth 1 2 and X2M 13 14 8 Connect the booster heater power supply cable to ...

Страница 8: ...le the booster heater and the heat exchanger 3 Once every 2 year Anode Check if the anode is not deteriorated If the diameter of the anode has decreased with 10 mm or more make sure to replace it original diameter is 33 mm A4P K6M F2B K3M K7M 2 1 X4M 4a OPTIONAL X2M 21 20 Q2L 3 wayvalve 2 wayvalve 12 11 4 thermostat 2 1 3 5 6 7 8 9 10 13 19 thermal fuse 14 15 16 17 18 SOLARPUMP N L L2 L1 X3M 230V ...

Страница 9: ...in water supply is off Check that all shut off valves of the water circuit are completely open POSSIBLE CAUSES CORRECTIVE ACTION The thermal cut out s has have operated Check and reset button s Put the thermostat setting for domestic hot water on the indoor unit to 75 C Check if thermistor is correctly installed in thermistor socket The indoor unit EKHBH X is not operating Check the indoor unit EK...

Страница 10: ...4PW43396 1D Copyright Daikin ...

Отзывы: