Domestic hot water tank for air to water heat pump system

 

4PW43396-1D

 

Installation manual

 

3

 

Safety devices

 

 

Thermal protector — The booster heater in the domestic hot
water tank is equipped with a thermal protector. The thermal
protector is activated when the temperature becomes too high.
When activated, the protector has to be reset on the domestic
hot water tank by pressing the red button (for access, remove
the electrical box cover).

 

 

Pressure relief valve — A pressure relief valve (field supply) in
accordance with relevant local and national regulations, and with
an opening pressure of maximum 10 bar must be connected to
the pressure relief valve connection.

Water may drip from the discharge of the pressure relief valve
device.

 

Outlook diagram

 

Outlook diagram, see 

figure 2

.

 

Installation guidelines

 

Keep in mind the following guidelines when installing the domestic
hot water tank:

 

 

The installation location is frost-free.

 

 

Take  care that in the event of a leak, water cannot cause any
damage to the installation space and surroundings.

 

 

Make sure to make the piping in size 1" or more (and reduce to
3/4" at the inlet of the tank) as to have sufficient water volume in
the piping between indoor unit and domestic hot water tank.

 

 

Locate the domestic hot water tank in a suitable position to
facilitate ease of maintenance; remember access is required to
the electrical box. Refer to the grey-coloured zones indicated in

figure 2

.

 

 

Provide a connection for the pressure relief valve blow-off and
drain.

 

 

To  avoid back siphonage it is advised to install a non-return
valve on the water inlet of the domestic hot water tank in
accordance with local and national regulations.

 

Installing the domestic hot water tank

 

1

 

Check if all domestic hot water tank accessories (see

"Accessories" on page 1

) are enclosed.

 

2

 

When floor mounting, place the domestic hot water tank on a
level surface. If required, adjust the legs at the bottom. When
wall mounting (only for EKHWET150A3V3 model), make sure
the wall is sturdy. In both cases, make sure the domestic hot
water tank is mounted level.

 

3

 

Make sure to respect the service space as indicated in 

figure 2

.

 

Connecting the water circuits

 

Refer to the chapter "Typical application examples" described in the
installation manual delivered with the indoor unit for details on
connecting the water circuits and the motorised 3-way valve.

Make sure to insulate all water pipes and connections.

 

Connecting the 3-way valve

 

1

 

Refer to 

figure 3

 before making the connection.

 

2

 

Installation position.

It is advised to connect the 3-way valve as close as possible to
the indoor unit. It can be installed in accordance with one of the
following four configurations.

 

3

 

Unpack the 3-way valve body and 3-way valve motor.

Verify that following accessories are provided with the motor.

 

 

The domestic hot water tank relief valve connections
may not be used for other purpose.

 

 

Do not install heaters without thermal cut-outs.

 

The electrical box lid must only be opened by a
licensed electrician.

Switch off the power supply before opening the
electrical box lid.

 

figure A

figure B

figure C

figure D

 

1

 

From 

 

AD

 

 

 

indoor unit

 

2

 

To domestic hot water tank

 

3

 

To room heating

 

1

 

Sleeve

 

2

 

Valve motor cover

 

3

 

Screw

 

4

 

Scale

1

2

3

1

3

2

1

2

3

1

3

2

1

2

3

4

Содержание Altherma EKHWE150A3V3

Страница 1: ...INSTALLATION MANUAL EKHWE150A3V3 EKHWET150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 Domestic hot water tank for air to water heat pump system ...

Страница 2: ... 30 30 50 700 300 440 500 4 5 30 30 700 400 705 220 255 280 35 115 775 1150 13 21 355 440 50 EKHWE150 300 EKHWET150 D1 1150 775 280 255 35 545 1525 925 280 410 35 545 1525 851 210 410 27 660 H1 H2 H3 H4 H5 Ø D1 150 200 EKHWE 300 A A A A 16 16 16 400 400 0 400 77 111 38 67 44 2 1 3 ...

Страница 3: ... EKHWET150A3V3 EKHWE200A3V3 EKHWE200A3Z2 EKHWE300A3V3 EKHWE300A3Z2 Domestic hot water tank for air to water heat pump system Installation manual READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQU...

Страница 4: ...stic hot water quality must be according to EN directive 98 83 EC A drain device should be installed on the cold water connection on the domestic hot water tank For safety reasons it is not allowed to add ethylene glycol to the water circuit Adding ethylene glycol might lead to contamination of the domestic water if a leakage would occur in the heat exchanger coil It is important that the storage ...

Страница 5: ...d back siphonage it is advised to install a non return valve on the water inlet of the domestic hot water tank in accordance with local and national regulations Installing the domestic hot water tank 1 Check if all domestic hot water tank accessories see Accessories on page 1 are enclosed 2 When floor mounting place the domestic hot water tank on a level surface If required adjust the legs at the ...

Страница 6: ...tions refer to Field wiring in the indoor unit installation manual supplied with the EKHBH X unit Installation in accordance with figure A and figure B Installation in accordance with figure C and figure D If the valve is not positioned in this way before mounting the motor the valve will give way to both domestic water and room heating during operation Installation in accordance with figure A and...

Страница 7: ...ector connected to the contactor K3M in the socket X13A on the PCB 5 Plug the thermistor cable connector in the socket X9A on the PCB 6 Connect the prewired earth wires of the terminal block X3M and X4M to the earthing screw 7 Connect the booster heater power supply and thermal protection cable field supply to terminal X4M earth 1 2 and X2M 13 14 8 Connect the booster heater power supply cable to ...

Страница 8: ...le the booster heater and the heat exchanger 3 Once every 2 year Anode Check if the anode is not deteriorated If the diameter of the anode has decreased with 10 mm or more make sure to replace it original diameter is 33 mm A4P K6M F2B K3M K7M 2 1 X4M 4a OPTIONAL X2M 21 20 Q2L 3 wayvalve 2 wayvalve 12 11 4 thermostat 2 1 3 5 6 7 8 9 10 13 19 thermal fuse 14 15 16 17 18 SOLARPUMP N L L2 L1 X3M 230V ...

Страница 9: ...in water supply is off Check that all shut off valves of the water circuit are completely open POSSIBLE CAUSES CORRECTIVE ACTION The thermal cut out s has have operated Check and reset button s Put the thermostat setting for domestic hot water on the indoor unit to 75 C Check if thermistor is correctly installed in thermistor socket The indoor unit EKHBH X is not operating Check the indoor unit EK...

Страница 10: ...4PW43396 1D Copyright Daikin ...

Отзывы: