3 Preparation
Installation manual
4
EBLQ+07CAV3
Daikin Altherma low temperature monobloc
4P403578-1C – 2016.02
5×
3×
2
Remove the accessories.
1×
1×
1×
1×
a
b
c
d
2×
1×
2×
f
e
g
a
General safety precautions
b
Addendum book for optional equipment
c
Outdoor unit installation manual
d
Operation manual
e
Sealing ring for shut-off valve
f
Shut-off valve
g
Unit mounting plate
3
Preparation
3.1
Preparing installation site
3.1.1
Installation site requirements of the
outdoor unit
Mind the following spacing guidelines:
≤1200
>250/400
>250/400
>250
>350
>350
(mm)
(mm)
a
b
b
a
a
Air outlet
b
Air inlet
INFORMATION
If shut-off valves are installed on the unit, provide a
minimum space of 400 mm at the air inlet side. If shut‑off
valves are NOT installed on the unit, provide a minimum
space of 250 mm.
If the system contains a domestic hot water tank, meet the following
requirements:
Maximum allowable distance
between outdoor unit and …
Distance
domestic hot water tank
10 m
3‑way valve
10 m
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging 10~43°C in cooling mode, –25~25°C
in space heating mode, and –25~35°C in domestic hot water
operation mode.
3.2
Preparing water piping
3.2.1
To check the water volume and flow rate
Minimum water volume
If
Then
The system contains a backup
heater
The minimum water volume is
10 l
(a)
The system does NOT contain a
backup heater
The minimum water volume is
20 l
(a)
(a)
The internal water volume of the outdoor unit NOT
included.
NOTICE
When circulation in each space heating loop is controlled
by remotely controlled valves, it is important that the
minimum water volume is guaranteed, even if all of the
valves are closed.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions.
NOTICE
If glycol was added to the water circuit, and the
temperature of the water circuit is low, the flow rate will
NOT be displayed on the user interface. In this case, the
minimum flow rate can be checked by way of the pump
test (check that the user interface does NOT display error
7H).
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating/operation).
See the installer reference guide for more information.
Minimum required flow rate
05+07 models
12 l/min
See the recommended procedure as described in
during commissioning" on page 18
.