6 Commissioning

Installation manual

19

EBLQ+07CAV3
Daikin Altherma low temperature monobloc
4P403578-1C – 2016.02

INFORMATION

▪ To  purge  air,  use  all  air  purge  valves  present  in  the

system. This includes the manual air purge valve of the
outdoor unit, as well as any field-supplied valves.

▪ For  the  location  of  the  manual  air  purge  valve,  see

"Components:  Outdoor  unit"  in  the  installer  reference
guide.

▪ If the system contains a backup heater, also use the air

purge  valve  of  the  backup  heater.  For  the  location  of
this valve, refer to "Components: Backup heater" in the
installer reference guide.

▪ If  the  system  contains  valve  kit  EKMBHBP1,  it  is

required to – during the air purge – manually switch the
position  of  the  valve  kit's  3‑way  valve  by  turning  its
knob, this to prevent air from remaining in the bypass.
For  more  information,  refer  to  the  instruction  sheet  of
the valve kit.

6.2.2

To perform a test run

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 12

.

2

Go  to  [A.7.1]: 

  >  Installer  settings  >  Commissioning  >  Test

run.

3

Select a test and press 

Example: 

Heating.

4

Select OK and press 

.

Result: 

The  test  run  starts.  It  stops  automatically  when  done

(±30 min). To stop it manually, press 

, select OK and press 

.

INFORMATION

When  starting  up  the  system  in  a  cold  climate,  and  NO
backup  heater  kit  (EKMBUHCA3V3  or  EKMBUHCA9W1)
was  installed,  it  may  be  required  to  start  up  with  a  small
water volume. To do this, gradually open the heat emitters.
As  a  result,  the  water  temperature  will  gradually  rise.
Monitor  the  inlet  water  temperature  ([6.1.6]  in  the  menu
structure) and make sure it does NOT drop below 15°C.

INFORMATION

If  2  user  interfaces  are  present,  you  can  start  a  test  run
from both user interfaces.

▪ The user interface used to start the test run displays a

status screen.

▪ The other user interface displays a "busy" screen. You

cannot  use  the  user  interface  as  long  as  the  "busy"
screen is shown.

6.2.3

To perform an actuator test run

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 12

.

2

Make  sure  the  room  temperature  control,  the  leaving  water
temperature  control  and  the  domestic  hot  water  control  are
turned OFF via the user interface.

3

Go  to  [A.7.4]: 

  >  Installer  settings  >  Commissioning  >

Actuator test run.

4

Select an actuator and press 

Example: 

Pump.

5

Select OK and press 

.

Result: 

The  actuator  test  run  starts.  It  automatically  stops  when

finished. To stop it manually, press 

, select OK and press 

.

Possible actuator test runs

▪ Booster heater test

▪ Backup heater (step 1) test

▪ Backup heater (step 2) test

▪ Pump test

INFORMATION

Make  sure  that  all  air  is  purged  before  executing  the  test
run. Also avoid disturbances in the water circuit during the
test run.

▪ 2-way valve test

▪ 3-way valve test

▪ Bivalent signal test

▪ Alarm output test

▪ Cooling/heating signal test

▪ Quick heat-up test

▪ Circulation pump test

6.2.4

To perform an underfloor heating screed
dryout

Prerequisite: 

Make sure there is ONLY 1 user interface connected

to your system to perform an underfloor heating screed dryout.

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Go  to  [A.7.2]: 

  >  Installer  settings  >  Commissioning  >  UFH

screed dryout.

2

Set a dryout program.

3

Select Start dryout and press 

.

4

Select OK and press 

.

Result: 

The  underfloor  heating  screed  dryout  starts.  It  stops

automatically  when  done.  To  stop  it  manually,  press 

,  select  OK

and press 

.

NOTICE

To perform an underfloor heating screed dryout, room frost
protection needs to be disabled ([2‑06]=0). By default, it is
enabled  ([2‑06]=1).  However,  due  to  the  "installer-on-site"
mode  (see  "Checklist  before  commissioning"),  room  frost
protection  will  be  automatically  disabled  for  12  hours  after
the first power-on.

If  the  screed  dryout  still  needs  to  be  performed  after  the
first  12  hours  of  power-on,  manually  disable  room  frost
protection  by  setting  [2‑06]  to  "0",  and  KEEP  it  disabled
until the screed dryout has finished. Ignoring this notice will
result in cracking of the screed.

NOTICE

For the underfloor heating screed dryout to be able to start,
make sure the following settings are met:

▪ [4‑00]=1

▪ [C‑02]=0

▪ [D‑01]=0

▪ [4‑08]=0

▪ [4‑01]≠1

Содержание Altherma EDLQ05CAV3

Страница 1: ...Installation manual Daikin Altherma low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3...

Страница 2: ...mi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 1...

Страница 3: ...ture Overview installer settings 17 6 Commissioning 18 6 1 Checklist before commissioning 18 6 2 Checklist during commissioning 18 6 2 1 To perform an air purge 18 6 2 2 To perform a test run 19 6 2 3...

Страница 4: ...o check the water volume and flow rate Minimum water volume If Then The system contains a backup heater The minimum water volume is 10 l a The system does NOT contain a backup heater The minimum water...

Страница 5: ...75 mm d Cable section 0 75 mm till 1 25 mm maximum length 20 m e If valve kit EKMBHBP1 is part of the system then the required cable section is 0 75 mm If valve kit EKMBHBP1 is NOT part of the system...

Страница 6: ...e unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to in...

Страница 7: ...condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the eva...

Страница 8: ...e piping from freezing Protection against freezing the glycol will prevent the liquid inside the piping from freezing Lowest expected outdoor temperature Prevent from bursting Prevent from freezing 5...

Страница 9: ...ter circuit For instructions see 6 Commissioning on page 18 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8...

Страница 10: ...power supply 1 Connect the main power supply 1 2 3 X4M 2 3 1 1 GND 2 L 3 N 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 is NOT part of the system connect the user interfa...

Страница 11: ...ted to the outdoor unit However if control box EKCB07CAV3 is present in the system you can also connect it to the control box To do this connect outdoor unit terminals X3M 1 2 to control box terminals...

Страница 12: ...r more than 1 hour or press again for more than 4 seconds the installer permission level switches back to End user To set the user permission level to Advanced end user 1 Go to the main menu or any of...

Страница 13: ...See also illustrations below Domestic hot water pump installed for Instant hot water Disinfection c f a g h b c h b a d f e g a Outdoor unit b Tank c Domestic hot water pump d Heater element e Non ret...

Страница 14: ...nction between the detection of an alarm and the detection of a power failure See also table below Alarm output logic A 2 2 F 3 D 08 Optional external kWh meter 1 0 No NOT installed 1 Installed 0 1 pu...

Страница 15: ...g water In case a minimum temperature difference is required for the good operation of the heat emitters in heating mode A 3 1 3 2 9 0A Cooling required temperature difference between entering and lea...

Страница 16: ...cool down cycle 5 2 6 Domestic hot water control Code Description A 4 1 6 0D Domestic hot water Type 0 Reheat only Only reheat operation is allowed 1 Reheat sched Same as 2 but between the scheduled h...

Страница 17: ...ones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp ra...

Страница 18: ...r heater Booster heater circuit breaker F2B on the switch box of the control box is turned ON The correct pipe size is installed and the pipes are properly insulated There are no water leaks inside th...

Страница 19: ...eaving water temperature home page room temperature home page and domestic hot water home page are turned OFF 1 Set the user permission level to Installer See To set the user permission level to Insta...

Страница 20: ...lation to maintaining the unit Explain the user about energy saving tips as described in the operation manual 7 1 About locking and unlocking If required it is possible to lock the buttons of the main...

Страница 21: ...door unit See the internal wiring diagram supplied with the unit on the inside of the outdoor unit switch box cover The abbreviations used are listed below Position in switch box hydro switch box A1P...

Страница 22: ...M L PCB3 PCB2 PCB1 GRN GRN GRN RED RED RED RED 1 S502 2 3 4 5 6 7 8 9 10 11 S503 1 2 3 4 5 S501 1 2 3 4 5 SW5 SW2 SW1 SW3 A 1 2 3 4 DB1 DB2 HL402 HN402 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 1 2 3 4 5 6 7...

Страница 23: ...L1 HN1 30A V3 S10 3 2 1 MR30_A MR30_B 1 2 S20 S50 1 2 3 4 5 1 2 3 4 DP2 DP1 MR307 MR306 FU1 T3 15A V401 DB401 1 2 3 4 5 6 1 2 3 4 1 2 3 4 5 6 7 WHT YLW ORG BLU RED Y1E M S1NPH S60 S90 S40 R3T t R2T t...

Страница 24: ...A X7A X21A K4R K6R X10A X14A X15A X18A 1 2 3 4 5 3 1 1 3 1 2 A1P TR1 M1P S1L N L GND PWM PE MS 3 t t t R3T R4T R1T X10A X1A X5M X3M X5Y A2P 4 3 4 3 2 1 2 1 X2M 23 X2M 22 X2M 21 X2M 20 X8M 9 X8M 8 X8M...

Страница 25: ...onvector only for wireless On OFF thermostat 4D094176 1C_Page 8 User interface Remote user interface Option box DHW pump output Max load 2 A inrush 230 V AC 1 A continuous DHW pump Dual setpoint appli...

Страница 26: ...PCB A3P On OFF thermostat PC power circuit A3P Heat pump convector A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat B1L Flow sensor C110 C112 Capac...

Страница 27: ...mistor air R1H A3P Humidity sensor R4T A1P Inlet water thermistor R5T Domestic hot water thermistor R6T A1P External outdoor ambient thermistor R6T A4P External indoor ambient thermistor S1L Flow swit...

Страница 28: ...a 2 Only for heat pump convector Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indo...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...4P403578 1C 2016 02 Copyright 2015 Daikin...

Отзывы: