Application guidelines
Installer reference guide
37
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
6.4.3 Normal kWh rate power supply
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/5 and X5M/6. See
103].
Power meter type
In case of…
Use a… power meter
▪
Single-phase outdoor unit
▪
Backup heater supplied from a single-
phase grid (i.e. the backup heater
model is *3V or *6V connected to a
single-phase grid)
Single-phase
(*3V, *6V (6V): 1N~ 230 V)
▪
Three-phase outdoor unit
▪
Backup heater supplied from a three-
phase grid (i.e. the backup heater
model is *9W or *6V connected to a
three-phase grid)
Three-phase
(*6V (6T1): 3~ 230 V)
(*9W: 3N~ 400 V)
Example
Single-phase power meter
Three-phase power meter
b
580
1 50
0
0
c
c
f
e
d
g
A
B
C
a
A
Outdoor unit
B
Indoor unit
C
DHW tank
a
Electrical cabinet (L
1
/N)
b
Power meter (L
1
/N)
c
Fuse (L
1
/N)
d
Outdoor unit (L
1
/N)
e
Indoor unit (L
1
/N)
f
Backup heater (L
1
/N)
g
Booster heater (L
1
/N)
b
580
1 50
0
0
g
f
e
h
A
B
C
c
c
d
a
A
Outdoor unit
B
Indoor unit
C
DHW tank
a
Electrical cabinet (L
1
/L
2
/L
3
/N)
b
Power meter (L
1
/L
2
/L
3
/N)
c
Fuse (L
1
/L
2
/L
3
/N)
d
Fuse (L
1
/N)
e
Outdoor unit (L
1
/L
2
/L
3
/N)
f
Indoor unit (L
1
/L
2
/L
3
/N)
g
Backup heater (L
1
/L
2
/L
3
/N)
h
Booster heater (L
1
/N)