10
|
Configuration
Installer reference guide
153
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
10.5.5 Space heating
Overview
The following items are listed in the submenu:
4
Space heating/cooling
Tank
Additional zone
Main zone
User settings
[4]
Space heating/cooling
[4.1]
Operation mode
[4.2]
Operation mode schedule
[4.3]
Operation range
[4.4]
Number of zones
[4.5]
Pump operation mode
[4.6]
Unit type
[4.7]
Pump limitation
[4.8]
Pump limitation
[4.9]
Pump outside range
[4.A]
Increase around 0°C
[4.B]
Overshoot
[4.C]
Antifrost
About space operation modes
This unit is a heating only model. The system can heat up a space, but NOT cool
down a space.
Operation range
Depending on the average outdoor temperature, the operation of the unit in space
heating is prohibited.
#
Code
Description
[4.3.1]
[4-02]
Space heating off temperature
: When
the averaged outdoor temperature rises above
this value, space heating is turned off.
▪
14°C~35°C
Number of zones
The system can supply leaving water to up to 2 water temperature zones. During
configuration, the number of water zones must be set.
#
Code
Description
[4.4]
[7‑02]
▪
0:
Single zone
Only one leaving water temperature zone:
a
a
Main LWT zone