Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.3.5
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
9.3.6
[5-00]
R/W
0: Allowed
1: Not allowed
9.3.7
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.3.8
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
└─
Booster heater
9.4.1
[6-02]
R/W
0~10kW, step: 0,2kW
0
kW
9.4.3
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.4.4
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
└─
Emergency
9.5.1
[4-06]
R/W
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.5.2
[7-06]
R/W
0: Disabled
1: Enabled
└─
Balancing
9.6.1
[5-02]
R/W
0: Disabled
1: Enabled
9.6.2
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.6.3
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.6.4
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour
9.6.5
[8-00]
R/W
0~20 min, step 1 min
1 min
9.6.6
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.6.7
[8-04]
R/W
0~95 min, step: 5 min
95 min
Installer settings
9.7
[4-04]
0: Intermittent
1: Continuous
2: Off
└─
Benefit kWh power supply
9.8.2
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.8.3
[D-05]
R/W
0: Forced off
1: As normal
9.8.4
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Smart grid
9.8.6
0: No
1: Yes
9.8.8
0~20 kW, step: 0,5 kW
20 kW
└─
Power consumption control
9.9.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.9.2
[4-09]
R/W
0: Current
1: Power
9.9.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.9.4
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.9.5
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.9.6
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.9.7
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.9.8
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.9
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.A
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.B
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.C
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.D
[4-01]
0: None
1: BSH
2: BUH
└─
Energy metering
9.A.1
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
Capacity step 1
Additional capacity step 2
Equilibrium
Equilibrium temperature
Operation
Capacity
BSH eco timer
Operation
Space heating priority
Priority temperature
Offset BSH setpoint
Anti-recycle timer
Emergency
HP Forced OFF
Minimum running timer
Maximum running timer
Additional timer
Water pipe freeze prevention
Limit 3
Power consumption control
Type
Limit
Limit 1
Limit 2
Limit 4
Priority heater
Electricity meter 1
Limit 3
Limit 4
Limit
Limit 1
Limit 2
Allow electric heaters
Allow heater
Allow pump
Benefit kWh power supply
Limit setting kW
(*1) *3V_
(*2) *6V_
(*3) *9W
(#) Setting is not applicable for this unit.
4P629095-1 - 2020.09