8 Troubleshooting
Operation manual
19
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620243-1 – 2020.06
8.1
To display the help text in case of
a malfunction
In case of a malfunction, the following will appear on the home
screen depending on the severity:
▪
: Error
▪
: Malfunction
You can get a short and a long description of the malfunction as
follows:
1
Press the left dial to open the main menu and go to
Malfunctioning
.
Result:
A short description of the error and the error
code is displayed on the screen.
2
Press in the error screen.
Result:
A long description of the error is displayed
on the screen.
8.2
To check the malfunction history
Conditions:
The user permission level is set to advanced end user.
1
Go to [8.2]:
Information
>
Malfunction history
.
You see a list of the most recent malfunctions.
8.3
Symptom: You are feeling too cold
(hot) in your living room
Possible cause
Corrective action
The desired room temperature is
too low (high).
Increase (decrease) the desired
room temperature. See
change the desired room
temperature"
If the problem recurs daily, do
one of the following:
▪ Increase (decrease) the room
temperature preset value. See
the user reference guide.
▪ Adjust the room temperature
schedule. See
14].
The desired room temperature
cannot be reached.
Increase the desired leaving
water temperature in accordance
with the heat emitter type. See
"5.6.3 To change the desired
leaving water temperature"
13].
The weather-dependent curve is
set incorrectly.
Adjust the weather-dependent
curve. See
8.4
Symptom: The water at the tap is
too cold
Possible cause
Corrective action
You ran out of domestic hot
water because of unusual high
consumption.
If you immediately need domestic
hot water, activate the DHW tank
Powerful operation
. However,
this consumes extra energy. See
"5.7.4 Using DHW powerful
operation"
If the problems recurs daily, do
one of the following:
▪ Increase
the
DHW
tank
temperature preset value. See
the user reference guide.
▪ Adjust
the
DHW
tank
temperature
schedule.
Example:
Program
to
additionally
heat
up
the
DHW tank to a preset value
(
Eco setpoint
= lower tank
temperature) during the day.
See
14].
The desired DHW tank
temperature is too low.
8.5
Symptom: Heat pump failure
When the heat pump fails to operate, the backup heater (if available)
and/or booster heater (if available) can serve as an emergency
heater. It then takes over the heat load either automatically or by
manual interaction.
▪ When
Emergency
is set to
Automatic
and a heat pump failure
occurs, the backup heater automatically takes over the heat load,
and the booster heater in the optional tank takes over the
domestic hot water production.
▪ When
Emergency
is set to
Manual
and a heat pump failure
occurs, the domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main menu screen and confirm whether the
backup heater and/or booster heater can take over the heat load
or not.
▪ Alternatively, when
Emergency
is set to:
▪
auto SH reduced/DHW on
, space heating is reduced but
domestic hot water is still available.
▪
auto SH reduced/DHW off
, space heating is reduced and
domestic hot water is NOT available.
▪
auto SH normal/DHW off
, space heating operates as
normally but domestic hot water is NOT available.
Similarly as in
Manual
mode, the unit can take the full load with
the backup heater and/or booster heater if the user activates this
via the
Malfunctioning
main menu screen.
When the heat pump fails,
or
will appear on the user
interface.
Possible cause
Corrective action
Heat pump is damaged.
19].
INFORMATION
When the backup heater or booster heater takes over the
heat load, electricity consumption will be considerably
higher.