6 Electrical installation
Installation manual
13
ETVH/9W
Daikin Altherma 3 H MT F
4P634880-1 – 2021.03
—
A
1 2 3
a
B
A
B
1 2 3
X2M
X1A
X11YA
X11YB
X11Y
X1M
a
a
Interconnection cable (=main power supply)
In case of preferential kWh rate power supply
Interconnection
cable (= main
power supply)
Wires: (3+GND)×1.5 mm²
Normal kWh rate
power supply
Wires: 1N
Maximum running current: 6.3 A
Preferential kWh
rate power supply
contact
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply
contact: 16 V DC detection (voltage
supplied by PCB). The voltage-free
contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
[9.8]
Benefit kWh power supply
Connect X11Y to X11YB.
A
10
9
S1S
N
L
5
6
1N~, 50 Hz,
230 V AC, 6.3 A
1 2 3
a
b
c
B
A
B
5 6
1 2 3
X2M
X1A
X11YA
X11YB
X11Y
X5M
9 10
X1M
a
b
c
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
3
Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X11Y to X11YB. The necessity of separate normal kWh
rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
6.3.2
To connect the backup heater power
supply
Backup heater
type
Power supply
Wires
*6V
1N~ 230 V (6V3)
2+GND
3~ 230 V (6T1)
3+GND
*9W
3N~ 400 V
4+GND
[9.3]
Backup heater