8 Commissioning

Installation manual

30

ETVH/9W

Daikin Altherma 3 H MT F

4P634880-1 – 2021.03

8

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during the commissioning
and hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  MUST  remain  open  after
commissioning.

INFORMATION

Protective  functions  –  "Installer-on-site  mode"

.  The

software  is  equipped  with  protective  functions,  such  as
room antifrost. The unit automatically runs these functions
when necessary.

During  installation  or  service  this  behaviour  is  undesired.
Therefore, the protective functions can be disabled:

At  first  power-on:

  The  protective  functions  are

disabled  by  default.  After  12  hours  they  will  be
automatically enabled.

Afterwards:

  An  installer  can  manually  disable  the

protective  functions  by  setting  [9.G]: 

Disable

protections

=

Yes

.  After  his  work  is  done,  he  can

enable  the  protective  functions  by  setting  [9.G]:

Disable protections

=

No

.

Also see 

"Protective functions"

 [

4

 22].

8.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit MUST be closed. Power-up the
unit after it is closed.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

▪ Between the indoor unit and the valves (if applicable)

▪ Between  the  indoor  unit  and  the  room  thermostat  (if

applicable)

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

automatic air purge

 valves are open.

The 

pressure  relief  valve

  purges  water  when  opened.

Clean water MUST come out.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions. See "To check the water volume and flow rate"
in 

"5.1 Preparing water piping"

 [

4

 8].

The 

domestic hot water tank

 is filled completely.

8.2

Checklist during commissioning

The 

minimum  flow  rate

  during  backup  heater/defrost

operation  is  guaranteed  in  all  conditions.  See  "To  check
the  water  volume  and  flow  rate"  in 

"5.1  Preparing  water

piping"

 [

4

 8].

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

8.2.1

To check the minimum flow rate

1

Check the hydraulic configuration to find out which
space heating loops can be closed by mechanical,
electronic, or other valves.

2

Close all space heating loops that can be closed.

3

Start the pump test run (see 

"8.2.4 To perform an

actuator test run"

 [

4

 31]).

4

Read out the flow rate

(a)

 and modify the bypass valve

setting to reach the minimum required flow rate + 2 l/
min.

(a)

During pump test run, the unit can operate below the minimum
required flow rate.

Minimum required flow rate

20 l/min

Содержание Altherma 3 H MT F

Страница 1: ...datahub eu Installation manual Daikin Altherma 3 H MT F English Installation manual Daikin Altherma 3 H MT F ETVH12S18EA6V ETVH12S23EA6V ETVH12S18EA9W ETVH12S23EA9W ETVX12S18EA6V ETVX12S23EA6V ETVX12S...

Страница 2: ...u vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Страница 3: ...nfiguration wizard 22 7 2 1 Configuration wizard Language 22 7 2 2 Configuration wizard Time and date 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configur...

Страница 4: ...NING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Install the tundish away from any electrical device Possible consequence Elec...

Страница 5: ...e handles at the back and at the bottom to carry the unit b a a b a Handles at the back of the unit b Handles at the bottom of the unit Carefully tilt the unit to the back so that the handles become v...

Страница 6: ...the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in th...

Страница 7: ...he pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 45 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into p...

Страница 8: ...water volume and flow rate Minimum water volume Check that the total water volume in the installation is higher than the minimum water volume the internal water volume of the indoor unit NOT included...

Страница 9: ...are field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressure bypass valve in the space heating water circuit Mind the minimum water volume when...

Страница 10: ...tion is then lower than assumed As a result the hydraulic components might freeze up after all Take preventive actions to ensure a minimal exposure of the glycol to air Types of glycol The types of gl...

Страница 11: ...unit NOTICE The distance between the high voltage and low voltage cables should be at least 50 mm 6 1 About electrical compliance Only for the backup heater of the indoor unit See 6 3 2 To connect the...

Страница 12: ...6 Room sensor offset Item Description WLAN module See Installation manual of the WLAN module Addendum book for optional equipment Installer reference guide Use the cable delivered with the WLAN modul...

Страница 13: ...10 9 S1S N L 5 6 1N 50 Hz 230 V AC 6 3 A 1 2 3 a b c B A B 5 6 1 2 3 X2M X1A X11YA X11YB X11Y X5M 9 10 X1M a b c a Interconnection cable main power supply b Normal kWh rate power supply c Preferential...

Страница 14: ...tting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or...

Страница 15: ...erent for a NC normally closed valve and a NO normally open valve A M2S B A B 21 28 X2M B 21 29 X2M NO NC 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity me...

Страница 16: ...als as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1...

Страница 17: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 46 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the approp...

Страница 18: ...able with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the...

Страница 19: ...X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter...

Страница 20: ...ive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory D Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the indoor...

Страница 21: ...via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settin...

Страница 22: ...ed This setting is read only Code Description 9 2 1 E 05 a E 06 a E 07 a Integrated The backup heater will also be used for domestic hot water heating a Use the menu structure instead of the overview...

Страница 23: ...staller the possibility to indicate whether the system is filled with glycol or water This is important in case glycol is used to protect the water circuit against freezing If NOT set correctly the li...

Страница 24: ...ing 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means...

Страница 25: ...is heated according to a schedule and between the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the op...

Страница 26: ...t curves 427 7 3 2 2 points curve Define the weather dependent curve with these two setpoints Setpoint X1 Y2 Setpoint X2 Y1 Example Y1 Y2 X1 X2 a Item Description a Selected weather dependent zone Mai...

Страница 27: ...ng Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather depend...

Страница 28: ...frost protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 External room thermostat type for the main zone 1 1 contact The used exter...

Страница 29: ...ectrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevent...

Страница 30: ...ation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable B...

Страница 31: ...ser permission level to Installer See To change the user permission level 421 2 Go to A 2 Commissioning Actuator test run 3 Select a test from the list Example Pump 4 Select OK to confirm Result The a...

Страница 32: ...sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to k...

Страница 33: ...ating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from out...

Страница 34: ...ump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor Exte...

Страница 35: ...rt Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermost...

Страница 36: ...core signal 2 core 2 core 2 core 2 core 2 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P634880 1 2021 03 Copyright 2021 Daikin 4P634880 1 0000000R Verantwortung f r Energie und Umwelt...

Отзывы: