13
|
Maintenance and service
Installer reference guide
248
EPRA14~18D + ETV23E
Daikin Altherma 3 H HT F
4P644738-1A – 2022.03
3
Close the valve (if equipped) of the water circuit towards the expansion vessel.
4
Remove the cap on the bottom of the magnetic filter/dirt separator.
5
Connect a drain hose to the bottom of the water filter.
6
Open the valve on the bottom of the water filter to drain water from the
water circuit. Collect the drained water in a bottle, sink,… using the installed
drain hose.
7
Remove the 2 clips that fix the water filter.
a
b
a
a
Clip
b
Magnetic filter/dirt separator
8
Remove the water filter.
9
Remove the drain hose from the water filter.
NOTICE
Although the water circuit is drained, some water may be spilled when removing the
magnetic filter/dirt separator from the filter housing. ALWAYS clean up spilled water.
13.5.2 To clean the water filter in case of trouble
1
Remove the water filter from the unit. See
NOTICE
To protect the piping connected to the magnetic filter/dirt separator from damage it
is recommended to perform this procedure with the magnetic filter/dirt separator
removed from the unit.
2
Unscrew the bottom of the water filter housing. Use an appropriate tool if
needed.
NOTICE
Opening the magnetic filter/dirt separator is ONLY required in case of severe issues.
Preferably this action is never to be done during the complete lifetime of the
magnetic filter/dirt separator.