9
|
Electrical installation
Installer reference guide
114
EPRA14~18D + ETV23E
Daikin Altherma 3 H HT F
4P644738-1A – 2022.03
1 2 3
1
2
3
3
(Optional)
Drain tube heater cable
:
▪
Make sure the heating element of the drain tube heater is completely inside
the drain tube.
▪
Route the cable through the frame.
▪
Connect the wires to the terminal block and the earth screw.
▪
Fix the cable with cable ties.
Wires: (2+GND)×0.75 mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115 W (0.5 A)
—