9/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Official Value
Installer setting at variance with
default value
Field settings table
9.I
[4-01]
R/W
0: None
1: BSH
2: BUH
9.I
[4-02]
R/W
14~35°C, step: 1°C
35°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
R/O
0: Intermittent
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.I
[4-07]
6
9.I
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.I
[4-09]
R/W
0: Current
1: Power
9.I
[4-0A]
R/W
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: Allowed
1: Not allowed
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
9.I
[5-0E]
1
9.I
[6-00]
R/W
2~40°C, step: 1°C
8°C
9.I
[6-01]
R/W
0~10°C, step: 1°C
2°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
3kW (*3)
0kW (*4)
9.I
[6-03]
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
9.I
[6-04]
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
9.I
[6-05]
0
9.I
[6-06]
0
9.I
[6-07]
0
9.I
[6-08]
R/W
2~20°C, step: 1°C
10°C
9.I
[6-09]
0
9.I
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.I
[6-0E]
R/W
(*3) [E-07]=0:
40~75°C, step: 1°C
60°C
(*3) [E-07]=5:
40~80°C, step: 1°C
80°C
(*4) : 40~65°C, step: 1°C
65°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
What is the desired reheat temperature?
What is the desired DHW production type?
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
What is the hysteresis to be used in reheat mode?
--
--
--
What is the desired comfort storage temperature?
What is the desired eco storage temperature?
--
Backup heater voltage
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the equilibrium temperature for the building?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
Backup heater configuration
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
Which electric heater has priority?
Which power limitation mode is required on the system?
Which power limitation type is required?
--
Emergency
Operation permission of the booster heater.
Below which outdoor temperature is heating allowed?
The temperature difference determining the heat pump OFF temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
Space heating priority temperature.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
Water pipe freeze prevention
Space heating priority.
--
--
What is the capacity of the backup heater step 2?
--
The temperature difference determining the heat pump ON temperature.
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*
(#) Only applicable in Swedish language.
4P586458-1 - 2019.07
Содержание Altherma 3 H HT EPRA14DAW1
Страница 258: ......
Страница 259: ......
Страница 260: ...4P587502 1A 2020 01 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...