9
|
Configuration
Installer reference guide
191
EPRA14~W1 + ETVH/9W(G)
Daikin Altherma 3 H HT F
4P587502-1A – 2020.01
NOTICE
Make sure to set the value of [5‑01] at least 1°C higher than the value of [C‑03].
Electricity and gas prices
INFORMATION
To set electricity and gas price values, do NOT use overview settings. Set them in the
menu structure instead ([7.5.1], [7.5.2], [7.5.3], and [7.6]). For more information on
how to set the energy prices, see the operation manual and the user reference
guide.
INFORMATION
Solar panels.
If solar panels are used, set the electricity price value very low to
promote the use of the heat pump.
#
Code
Description
[7.5.1]
N/A
User settings
>
Electricity price
>
High
[7.5.2]
N/A
User settings
>
Electricity price
>
Medium
[7.5.3]
N/A
User settings
>
Electricity price
>
Low
[7.6]
N/A
User settings
>
Gas price
Alarm output
Alarm output
#
Code
Description
[9.D]
[C–09]
Alarm output
: Indicates the logic of the alarm
output on the digital I/O PCB during
malfunctioning.
▪
0
Abnormal
: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
▪
1
Normal
: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).
Alarm output logic
[C-09]
Alarm
No alarm
No power supply
to unit
0
Closed output
Open output
Open output
1
Open output
Closed output
Содержание Altherma 3 H HT EPRA14DAW1