www.DaikinApplied.com 73
IOM 1206-7 • TRAILBLAZER
™
MODEL AGZ CHILLERS
Table 64: 3 Fans per Circuit - With 1 Fan VFD per Circuit
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X5
Fan 11
On On On --
--
--
Fan Output 2
UC DO4
Fan 12
On On --
--
--
Fan Output 3
UC DO5
Fan 13
On
Condenser SV UC X7
SV 11
On
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X6
Fan 21
On On On --
--
--
Fan Output 2
UC DO8
Fan 22
On On --
--
--
Fan Output 3
UC DO9
Fan 23
On --
--
--
Condenser SV UC X8
SV 21
On --
--
--
Table 65: 3 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X5
Fan 11
On
On --
--
--
Speed Signal 2 UC X2
Fan 12/13
On On --
--
--
Condenser SV UC X7
SV 11
On On
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X6
Fan 21
On
On --
--
--
Speed Signal 2 UC X3
Fan 22/23
On On --
--
--
Condenser SV UC X8
SV 21
On On
--
Figure 56: 4 Fans per Circuit - Unit Numbering Schematic
Table 66: 4 Fans per Circuit - Without Fan VFD
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Fan Output 1
UC DO3
Fan 11 On On On On --
--
Fan Output 2
UC DO4
Fan 12
On On --
--
Fan Output 3
UC DO5
Fan 13
On On On --
--
Fan Output 4
UC DO6
Fan 14
On --
--
Condenser SV UC X7
SV 11
On On On --
--
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Fan Output 1
UC DO7
Fan 21 On On On On --
--
Fan Output 2
UC DO8
Fan 22
On On --
--
Fan Output 3
UC DO9
Fan 23
On On On --
--
Fan Output 4
UC DO10
Fan 24
On --
--
Condenser SV UC X8
SV 21
On On On --
--
Table 67: 4 Fans per Circuit - With 1 Fan VFD per Circuit
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X5
Fan 11/13 On On On On --
--
Fan Output 2
UC DO4
Fan 12
On On --
--
Fan Output 4
UC DO6
Fan 14
On --
--
Condenser SV UC X7
SV 11
On On On --
--
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X6
Fan 21/23 On On On On --
--
Fan Output 2
UC DO8
Fan 22
On On --
--
Fan Output 4
UC DO10 Fan 24
On --
--
Condenser SV UC X8
SV 21
On On On --
--
Table 68: 4 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X5
Fan 11/13 On On On --
--
--
Speed Signal 2 UC X2
Fan 12/14
On --
--
--
Condenser SV UC X7
SV 11
On On
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X6
Fan 21/23 On On On --
--
--
Speed Signal 2 UC X3
Fan 22/24
On --
--
--
Condenser SV UC X8
SV 21
On On
--
Control Panel
Fan 11
Fan 12
Fan 21
Fan 23
Fan 13
Fan 24
Fan 22
Fan 14
4-Fan Unit Locations and Numbering