IOM 1206-7 • TRAILBLAZER
™
MODEL AGZ CHILLERS
38 www.DaikinApplied.com
e
leCTrICal
d
aTa
Table 16: Electrical Data - Single Point (60/50 Hz)
Table 17: Electrical Data - Single Point (60/50 Hz)
Model
Size
Voltage /
Freq .
Single Point Field Data
Ratings
Lug Range
MCA RFS MFS
Power Block
Disconnect
Switch
120E
208V/60
534
600
600
(2) 6-500MCM (2) 3/0-500MCM
230V/60
534
600
600
(2) 6-500MCM (2) 3/0-500MCM
380V/60
330
400
400
(1) 2-600MCM (2) 3/0-500MCM
460V/60
261
300
300
(1) 2-600MCM (2) 3/0-500MCM
575V/60
234
250
250
(1) 2-600MCM (2) 3/0-500MCM
400V/50
261
300
300
(1) 2-600MCM (2) 3/0-500MCM
130E
208V/60
569
700
700
(2) 6-500MCM (3) 2/0-400MCM
230V/60
569
700
700
(2) 6-500MCM (3) 2/0-400MCM
380V/60
358
400
450
(1) 2-600MCM (2) 3/0-500MCM
460V/60
284
350
350
(1) 2-600MCM (2) 3/0-500MCM
575V/60
239
250
250
(1) 2-600MCM (2) 3/0-500MCM
400V/50
284
350
350
(1) 2-600MCM (2) 3/0-500MCM
140E
208V/60
612
700
700
(2) 6-500MCM (3) 2/0-400MCM
230V/60
612
700
700
(2) 6-500MCM (3) 2/0-400MCM
380V/60
388
450
450
(1) 2-600MCM (2) 3/0-500MCM
460V/60
309
350
350
(1) 2-600MCM (2) 3/0-500MCM
575V/60
248
300
300
(1) 2-600MCM (2) 3/0-500MCM
400V/50
309
350
350
(1) 2-600MCM (2) 3/0-500MCM
150E
208V/60
640
700
700
(2) 6-500MCM (3) 2/0-400MCM
230V/60
640
700
700
(2) 6-500MCM (3) 2/0-400MCM
380V/60
410
500
500
(1) 2-600MCM (2) 3/0-500MCM
460V/60
328
400
400
(1) 2-600MCM (2) 3/0-500MCM
575V/60
252
300
300
(1) 2-600MCM (2) 3/0-500MCM
400V/50
328
400
400
(1) 2-600MCM (2) 3/0-500MCM
161E
208V/60
668
800
800
(2) 6-500MCM (3) 2/0-400MCM
230V/60
668
800
800
(2) 6-500MCM (3) 2/0-400MCM
380V/60
432
500
500
(1) 2-600MCM (2) 3/0-500MCM
460V/60
346
400
400
(1) 2-600MCM (2) 3/0-500MCM
575V/60
255
300
300
(1) 2-600MCM (2) 3/0-500MCM
400V/50
346
400
400
(1) 2-600MCM (2) 3/0-500MCM
170E
208V/60
734
800
800
(2) 6-500MCM (4) 4/0-500MCM
230V/60
734
800
800
(2) 6-500MCM (4) 4/0-500MCM
380V/60
442
500
500
(2) 6-500MCM (2) 3/0-500MCM
460V/60
355
400
400
(1) 2-600MCM (2) 3/0-500MCM
575V/60
309
350
350
(1) 2-600MCM (2) 3/0-500MCM
400V/50
355
400
400
(1) 2-600MCM (2) 3/0-500MCM
180E
208V/60
875
1000 1000
--
(4) 4/0-500MCM
230V/60
875
1000 1000
--
(4) 4/0-500MCM
380V/60
479
500
500
(2) 6-500MCM (2) 3/0-500MCM
460V/60
394
450
450
(1) 2-600MCM (2) 3/0-500MCM
575V/60
339
350
350
(1) 2-600MCM (2) 3/0-500MCM
400V/50
394
450
450
(1) 2-600MCM (2) 3/0-500MCM
NOTE:
MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Model
Size
Voltage /
Freq .
Single Point Field Data
Ratings
Lug Range
MCA RFS MFS
Power Block
Disconnect
Switch
190E
208V/60
848
1000 1000
(4) 2-600MCM (4) 4/0-500MCM
230V/60
848
1000 1000
(4) 2-600MCM (4) 4/0-500MCM
380V/60
508
600
600
(2) 6-500MCM (2) 3/0-500MCM
460V/60
424
500
500
(2) 6-500MCM (2) 3/0-500MCM
575V/60
348
400
400
(2) 6-500MCM (2) 3/0-500MCM
400V/50
424
500
500
(1) 2-600MCM (2) 3/0-500MCM
210E
208V/60
890
1000 1000
(4) 2-600MCM (4) 4/0-500MCM
230V/60
890
1000 1000
(4) 2-600MCM (4) 4/0-500MCM
380V/60
525
600
600
(2) 6-500MCM (2) 3/0-500MCM
460V/60
443
500
500
(2) 6-500MCM (2) 3/0-500MCM
575V/60
351
400
400
(2) 6-500MCM (2) 3/0-500MCM
400V/50
443
500
500
(1) 2-600MCM (2) 3/0-500MCM
225E
208V/60
943
1000 1000
(4) 2-600MCM (4) 4/0-500MCM
230V/60
943
1000 1000
(4) 2-600MCM (4) 4/0-500MCM
380V/60
551
600
600
(2) 6-500MCM (3) 2/0-400MCM
460V/60
469
500
500
(2) 6-500MCM (2) 3/0-500MCM
575V/60
359
400
400
(2) 6-500MCM (2) 3/0-500MCM
400V/50
469
500
500
(1) 2-600MCM (2) 3/0-500MCM
240E
208V/60
1071 1200 1200
(4) 2-600MCM (4) 4/0-500MCM
230V/60
1071 1200 1200
(4) 2-600MCM (4) 4/0-500MCM
380V/60
602
700
700
(2) 6-500MCM (3) 2/0-400MCM
460V/60
525
600
600
(2) 6-500MCM (2) 3/0-500MCM
575V/60
367
400
400
(2) 6-500MCM (2) 3/0-500MCM
400V/50
525
600
600
(1) 2-600MCM (2) 3/0-500MCM