IOM 1206-7 • TRAILBLAZER
™
MODEL AGZ CHILLERS
52 www.DaikinApplied.com
U
nIT
C
onTroller
o
peraTIon
Dynamic Set Point Ranges and Defaults
Some settings have different ranges of adjustment based
on other parameters and unit configuration. The condenser
settings that follow are applicable to four configuration groups:
1 - Models 30 to 70
2 - Models 75 to 240 with no fan VFDs or one VFD per circuit
3 - Models from 75 to 161 with 2 fan VFDs per circuit
4 - Models 170 to 240 with 2 fan VFDs per circuit
Table 49:
Configuration Group 1
Description
Default
Range
Condenser Target - 100% Circuit Capacity
37.78°C (100°F)
37.78 to 46.11°C (100 to 115°F)
Condenser Target - 67% Circuit Capacity
32.22°C (90°F)
32.22 to 46.11°C (90 to 115°F)
Condenser Target - 50% Circuit Capacity
32.22°C (90°F)
32.22 to 46.11°C (90 to 115°F)
Condenser Target - 33% Circuit Capacity
32.22°C (90°F)
32.22 to 40.56°C (90 to 105°F)
Fan Stage Up Deadband 1
11.11°C (20°F)
11.11 to 13.89°C (20 to 25°F)
Fan Stage Up Deadband 2
8.33°C (15°F)
8.33 to 11.11°C (15 to 20°F)
Fan Stage Up Deadband 3
5.56°C (10°F)
5.56 to 8.33°C (10 to 15°F)
Fan Stage Up Deadband 4
5.56°C (10°F)
5.56 to 8.33°C (10 to 15°F)
Fan Stage Down Deadband 4
5.56°C (10°F)
3.33 to 5.56°C (6 to 10°F)
Fan Stage Down Deadband 3
5.56°C (10°F)
3.33 to 5.56°C (6 to 10°F)
Fan Stage Down Deadband 2
5.56°C (10°F)
5.56 to 8.33°C (10 to 15°F)
Fan Stage Down Deadband 1
11.11°C (20°F)
8.33 to 11.11°C (15 to 20°F)
Table 50:
Configuration Group 2
Description
Default
Range
Condenser Target - 100% Circuit Capacity
37.78°C (100°F)
37.78 to 46.11°C (100 to 115°F)
Condenser Target - 67% Circuit Capacity
32.22°C (90°F)
32.22 to 43.33°C (90 to 110°F)
Condenser Target - 50% Circuit Capacity
29.44°C (85°F)
29.44 to 32.22°C (85 to 90°F)
Condenser Target - 33% Circuit Capacity
29.44°C (85°F)
29.44 to 40.56°C (85 to 105°F)
Fan Stage Up Deadband 1
11.11°C (20°F)
11.11 to 13.89°C (20 to 25°F)
Fan Stage Up Deadband 2
8.33°C (15°F)
8.33 to 11.11°C (15 to 20°F)
Fan Stage Up Deadband 3
5.56°C (10°F)
5.56 to 8.33°C (10 to 15°F)
Fan Stage Up Deadband 4
5.56°C (10°F)
5.56 to 8.33°C (10 to 15°F)
Fan Stage Down Deadband 4
5.56°C (10°F)
3.33 to 5.56°C (6 to 10°F)
Fan Stage Down Deadband 3
5.56°C (10°F)
3.33 to 5.56°C (6 to 10°F)
Fan Stage Down Deadband 2
8.33°C (15°F)
8.33 to 11.11°C (15 to 20°F)
Fan Stage Down Deadband 1
8.33°C (15°F)
8.33 to 11.11°C (15 to 20°F)
Table 51:
Configuration Group 3
Description
Default
Range
Condenser Target - 100% Circuit Capacity
40.56°C (105°F)
40.56 to 46.11°C (105 to 115°F)
Condenser Target - 50% Circuit Capacity, 75% Unit Capacity 40.56°C (105°F)
37.78 to 43.33°C (100 to 110°F)
Condenser Target - 50% Circuit Capacity, 50% Unit Capacity 32.22°C (90°F)
31.11 to 36.67°C (88 to 98°F)
Condenser Target - 50% Circuit Capacity, 25% Unit Capacity 26.67°C (80°F)
23.89 to 29.44°C (75 to 85°F)
Fan Stage Up Deadband 1
5.56°C (10°F)
2.78 to 8.33°C (5 to 15°F)
Fan Stage Up Deadband 2
2.78°C (5°F)
2.78 to 5.56°C (5 to 10°F)
Fan Stage Down Deadband 3
2.78°C (5°F)
2.78 to 5.56°C (5 to 10°F)
Fan Stage Down Deadband 2
2.78°C (5°F)
2.78 to 5.56°C (5 to 10°F)
Fan Stage Down Deadband 1
5.56°C (10°F)
5.56 to 8.33°C (10 to 15°F)
Содержание AGZ030E