Fieldbus Equivalent
Example: If 2008 MAXIMUM FREQ (see page 170) is set from
an external control system, an integer value of 1 corresponds
to 0 .1 Hz . All the read and sent values are limited to 16 bits
(-32768…32767) .
Table 20: Actual Signals in the Short Parameter View
Table 21: Parameters in the Short Parameter View
Actual signals in the short parameter view
No .
Name/Value
Description
FbEq
04
FAULT HISTORY
Fault history (read-only) . See Group 04: Fault History,
.
0401 LAST FAULT
Code of the latest fault .
1 = 1
Parameters in the short parameter view
No
Name/Value
Description
Default
1105 REF1 MAX
Defines the maximum value for external reference REF1.
E: 50 .0 Hz
U: 60 .0 Hz
13
ANALOG INPUTS
Analog input signal processing . See Group 13: Analog Inputs,
.
1301 MINIMUM AI1
Defines the minimum %-value that corresponds to minimum mA/(V) signal for analog input AI1.
1 .0%
21
START/STOP
Start and stop modes of the motor . See Group 21: Start/Stop,
2102 STOP FUNCTION
Selects the motor stop function .
COAST
22
ACCEL/DECEL
Acceleration and deceleration times . See Group 22: Accel/Decel,
.
2202 ACCELER TIME 1
Defines the acceleration time 1.
5 .0 s
2203 DECELER TIME 1
Defines the deceleration time 1.
5 .0 s
99
START-UP DATA
Language selection. Definition of motor set-up data. See Group 99: Start-Up Data,
9901 LANGUAGE
Selects the display language .
ENGLISH
9902 APPLIC DEFAULT
Selects the application macro
Daikin uses "HVAC"
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
230 V (200 V units)
400 V (400 V E units)
460 V (400 V U units)
9906 MOTOR NOM CURR
Defines the nominal motor current.
|
2N
9907 MOTOR NOM FREQ
Defines the nominal motor frequency.
E: 50 .0 Hz
U: 60 .0 Hz
9908 MOTOR NOM SPEED
Defines the nominal motor speed.
Type dependent
9909 MOTOR NOM POWER
Defines the nominal motor power.
P
N
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 31
OM 1190-1 • MD4 VFD