SiUS121736EA
Troubleshooting for SA Indoor Unit
Service Diagnosis
166
Note
Connector
Turn OFF the power supply
and wait for 10 minutes.
Turn OFF the power supply
and wait for 10 minutes.
NO
NO
Replace the fan motor.
Each resistance
between the pins is equal to or
lower than 1
Ω
.
Replace the fan motor.
Replace the fan PCB (A2P).
The HAP
lamp on the indoor
unit control PCB is blinking
while the HAP lamp on the
fan PCB is not
blinking.
YES
YES
Check the fan motor connectors.
Check No.02
Replace the fan PCB (A2P).
↓
When
A6
abnormality still
reoccurs, replace the fan
motor.
A
(R25084)
Model
*1
Fan motor connector
*2
Fuse
FDMQ Series
X8A
F2U