Si121858E
Outdoor Fan / Fan Motor
Removal Procedure
5
2. Outdoor Fan / Fan Motor
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Step
Procedure
Points
1. Remove the outdoor fan /
fan motor.
When reassembling, make
sure that the 2 hooks are
securely fastened.
Also, make sure not to
squash the harness.
1
2
Remove the 2 screws.
Slide upward and
remove the shield plate.
3
4
Disconnect the
connector [S70].
Cut the clamp.
[S70]: fan motor
5
6
Release the fan motor
lead wire from the 6
hooks and the groove.
Detach the wire clamp
material from the fan
motor lead wire.
When reassembling, wrap
around with the wire clamp
material 2 times or more
around the fan motor lead
wire at the position of the
clamp.
Shield plate
(R25760)
(R25761)
Clamp
[S70]
(R25762)
Wire clamp material Groove
Hook
Hook
Fan motor
lead wire
(R25763)
(to fan motor)
(to main PCB)
Clamp
Wire
clamp
material
(R25764)