SiBE12-933_A
Outdoor Unit
Removal Procedure
233
1.3
Removal of the PCB
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the outer panels
and plates such as the top
plate and the front panel.
Preparation
Remove the electrical box
according to the removal
procedure.
The control PCB is adopted
upside-down.
The lead-free solder (PbF) is
used on PCB. When
exchange, use exclusive
solder and soldering gun.
1. Remove the PCB
1
Remove the screw of
the cover of the
Electrical box.
2
Detach the insulation
sheet.
The trimmed part goes front.
3
Remove the 2 screws
of the terminal boards
to remove.
The terminal board is united
with temperature fuse.
4
Release the earth wire
from the hook.
(R7592)
Electrical box (cover)
M4×12
(R7593)
Central label
(R7594)
Insulation
sheet
Earth
terminals
(R7599)