BACnet IP Network Types

Single IP Subnet

In BACnet/IP networks with only IP subnet (IP domain), 

broadcast messages from a device (ex. 172.16.255.255 or 

0xBAC0) are sent to all other subnet members as IP broadcasts 

without requiring any additional configuration.

DHCP Networks

BACnet IP networks with DHCP use a server (typically a router 

or gateway) to automatically request network configuration 

parameters, such as IP addresses, to all devices.  DHCP-

enabled networks eliminate the need for a user to configure 

these settings manually since IP Addresses and other 

parameters are determined dynamically by the server. 

There are several important aspects to consider with DHCP-

enabled networks:

Aspect

Considerations

BBMDs

DHCP 

can not 

be used together with BBMDs, 

as the IP addresses are configured as static 

addresses and cannot change during operation.

Alarm 

recipient

In BACnet, alarm recipients are entered with 

their “Device Object Identifier” or their BACnet 

address. The IP address is part of the BACnet 

address and may not be changed for the alarm 

recipient. For this reason, option “Device Object 

Identifier” must always be used.

Access 

rights

If access rights are assigned based on IP 

address, such as firewalls, the address must 

be static. Access rights are based off of the 

UDP Port Number (ex. UDP 47808) or the MAC 

Address of the BACnet communication module.

IP version

The BACnet communication module supports 

IP Version 4, (i.e. IP devices with 32 bit 

addresses). 

Multiple IP Subnets

A BACnet/IP network may consist of multiple IP subnets 

assigned the same BACnet network number. In this case, 

a BBMD (BACnet Broadcast Management Device) allows 

broadcasts to be transmitted to all other BBMDs on the BACnet 

network.  BBMDs allow devices on one network to distribute 

broadcasts, or communicate, across multiple subnets. A 

BBMD also provides for foreign device registration. This allows 

a device on one network to communicate with a device on 

another network by using the BBMD to forward and route the 

messages.

The BACnet communication module can be registered as 

a BBMD device. This is done by registering the IP Address 

and subnet mask of the communication module as a Foreign 

Device with the BBMD.

Содержание 090016709

Страница 1: ...p Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH RCE RCS RDE RDS RDT RFS RPE RPS SWP and SWT ...

Страница 2: ...ght Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a Communication Module 6 Integration 6 Configuring the BACnet Communication Module 7 BACnet IP Addressing 7 Configurable Parameters 7 Service Information 9 Troubleshooting 9 Parts 9 Technical Support 9...

Страница 3: ...eath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release IM 916 1 May 2009 Modified Step 5 of To Configure the Module using the Keypad Display section Additional steps were added to describe how to properly set Given IP Address Given IP Mask or Given IP Ga...

Страница 4: ...ature numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Transportation Temperature 40 158 F 40 70 C Humidit...

Страница 5: ...flashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Group at 866 462 7829 for additional assistance if necessary BUS LED The BUS LED indicates the communication status between the BACnet communication module and the BACnet IP network Table 2 describes the...

Страница 6: ...r tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication module 6 Insert the board to board connector into the BACnet communication module Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet communication modu...

Страница 7: ...ntered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module installed correctly If the BACnet communication module is installed correctly and this menu still does not appear cycle power to the unit controller and repeat the procedure from Step 3 above 4 Modify the ...

Страница 8: ...et Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address Actual Gateway Address Item remains blank if the network is not connected when power is applied to the unit controller If DHCP is set to On the network automatically assigns this address If DHCP is se...

Страница 9: ...onfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required BBMD must be used if the BACnet client and BACnet server are located on different subnets Use the command tracert to check this Tracert shows all stations used to forward the signal to another segment...

Страница 10: ...Identifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access rights If access rights are assigned based on IP address such as firewalls the address must be static Access rights are based off of the UDP Port Number ex UDP 47808 or the MAC Address of the BACnet...

Страница 11: ......

Страница 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Отзывы: