9 Technical data

Installation manual

28

08SU EHVH08~16SU26CB6W

Daikin Altherma – Low temperature split

4P449980-1B – 2016.11

9.3

Wiring diagram: Indoor unit

See  the  internal  wiring  diagram  supplied  with  the  unit  (on  the  inside  of  the  indoor  unit  switch  box  cover).  The  abbreviations  used  are  listed
below.

Notes to go through before starting the unit

English

Translation

Notes to go through before
starting the unit

Notes to go through before
starting the unit

X1M

Main terminal

X2M

Field wiring terminal for AC

X5M

Field wiring terminal for DC

X6M, X7M

Backup heater terminal

Earth wiring

15

Wire number 15

Field supply

**

/12.2

Connection ** continues on page
12 column 2

1

Several wiring possibilities

Option

Not mounted in switch box

Wiring depending on model

PCB

Internal backup heater
configuration

Internal backup heater
configuration

 1N~, 230 V, 6 kW

 1N~, 230 V, 6 kW

 3~, 230 V, 6 kW

 3~, 230 V, 6 kW

 3N~, 400 V, 6 kW

 3N~, 400 V, 6 kW

User installed options

User installed options

 Bottom plate heater

 Bottom plate heater

 Remote user interface

 Remote user interface

 Ext. indoor thermistor

 External indoor thermistor

 Ext outdoor thermistor

 External outdoor thermistor

 Digital I/O PCB

 Digital I/O PCB

 Demand PCB

 Demand PCB

Main LWT

Main leaving water temperature

 On/OFF thermostat (wired)

 On/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 On/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Add LWT

Additional leaving water
temperature

 On/OFF thermostat (wired)

 On/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 On/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Position in switch box

English

Translation

Position in switch box

Position in switch box

Legend

A1P

Main PCB

A2P

User interface PCB

A3P

*

On/OFF thermostat (PC=power circuit)

A3P

*

Heat pump convector

A4P

*

Digital I/O PCB

A4P

*

Receiver PCB (Wireless On/OFF
thermostat)

A5P

Anode driver PCB

A8P

*

Demand PCB

DS1(A8P)

*

DIP switch

F1B

Overcurrent fuse backup heater

F2B

Overcurrent fuse booster heater

F1U, F2U

*

Fuse 5 A 250 V for digital I/O PCB

PHC1 (A4P)

*

Optocoupler input circuit

K*R

Relay on PCB

K1M, K2M

Contactor backup heater

K3M

Contactor booster heater

K5M

Safety contactor backup heater

M2P

#

Domestic hot water pump

M2S

#

Shut-off valve

Q*DI

#

Earth leakage circuit breaker

Q1L

Thermal protector backup heater

Q2L

Thermal protector booster heater

R1T (A3P)

*

Ambient sensor On/OFF thermostat

R2T

*

External sensor (floor or ambient)

R6T

*

External indoor or outdoor ambient
thermistor

R1H (A3P)

*

Humidity sensor

S1S

#

Preferential kWh rate power supply contact

S2S

#

Electrical meter pulse input 1

S3S

#

Electrical meter pulse input 2

S4S

#

Safety thermostat

S6S~S9S

#

Digital power limitation inputs

SS1 (A4P)

*

Selector switch

TR1

Power supply transformer

X*M

Terminal strip

X*Y

Connector

* =

Optional

# =

Field supply

Colours

BLK

Black

BRN

Brown

GRY

Grey

RED

Red

Содержание EHVH04SU18CB6W

Страница 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHVH04SU18CB6W EHVH08SU18CB6W EHVH08SU26CB6W EHVH11SU26CB6W EHVH16SU26CB6W...

Страница 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Страница 3: ...wizard Capacities energy metering 18 5 2 5 Space heating control 18 5 2 6 Domestic hot water control 19 5 2 7 Contact helpdesk number 19 5 3 Menu structure Overview installer settings 20 6 Commission...

Страница 4: ...unit is designed for indoor installation only and for ambient temperatures ranging from 5 35 C 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tigh...

Страница 5: ...r input signal b 23 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage...

Страница 6: ...gularities The maximum allowed deviation is 1 1 NOTICE Do NOT tilt the unit backwards 0 1 1 4 3 Connecting the refrigerant piping See the outdoor unit installation manual for all guidelines specificat...

Страница 7: ...mplies with the applicable legislation INFORMATION If you have to inspect the inside of the domestic hot water tank you can access it via the booster heater boss The connection of the water piping inv...

Страница 8: ...discharge pipe and tundish are delivered with the tank kit 180 l 260 l WARNING Install the tundish away from any electrical device Possible consequence Electric shock or fire NOTICE To ensure a free...

Страница 9: ...ate the system the domestic hot water tank needs to be filled completely Turning on the system when the tank is not full can damage the integrated booster heater and cause electrical errors 4 4 6 To i...

Страница 10: ...4 5 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M 1 2 3 1 2 3 X2M X5M X6YB X6YA X6Y X1A X19A 3031 a Legend see illustration below In c...

Страница 11: ...the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax 1 Connect the backup heater power supply For 6W...

Страница 12: ...eful NOT to damage it 3 Use the 2 screws in the accessory bag to fix the wallplate of the user interface to the sheet metal of the unit Be careful NOT to distort the shape of the backside of the user...

Страница 13: ...e illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 5 10 To connect the space heating ON OFF...

Страница 14: ...red by the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the booster heater power supply and the earth cable INFORMATION The non self resetting thermal cut...

Страница 15: ...methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via t...

Страница 16: ...installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 2 Basic configuration 5 2 1 Quick wizard Lan...

Страница 17: ...ermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the unit s user interface is turned ON Code Description A...

Страница 18: ...5 Space heating control Leaving water temperature Main zone Code Description A 3 1 1 1 N A Set point mode 0 Fixed Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for...

Страница 19: ...ion on the comfort setpoint for the room Leaving water temperature Emitter type Code Description A 3 1 1 7 9 0B Reaction time of the system 0 Quick Example Small water volume and fan coils 1 Slow Exam...

Страница 20: ...heater steps Forced off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW operation Contact type main Contact type add Digi...

Страница 21: ...To check the water volume in 3 2 Preparing water piping on page 4 The domestic hot water tank is filled completely The following is properly installed see the installation manual of the domestic hot w...

Страница 22: ...o to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished...

Страница 23: ...he PCB 8 1 1 Opening the indoor unit CAUTION The front panel is heavy Be careful NOT to jam your fingers when opening or closing the unit You just need to remove the front panel of the unit to gain ac...

Страница 24: ...be ensured that the water quality remains compliant with EU directive 98 83 EC Anode No maintenance or replacement required Pressure reducing valve of the domestic hot water tank kit Depending on loc...

Страница 25: ...th drain fill valve delivered as accessory h Water filter i Space heating water IN 1 1 4 F BSP j Space heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water h...

Страница 26: ...heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water hot water OUT 3 4 F BSP m Low voltage wiring intake 24 mm n High voltage wiring intake power supply cont...

Страница 27: ...nt OUT d Plate heat exchanger e Shut off valve with drain fill valve f 3 way valve g Backup heater h Flow sensor i Pressure relief valve j Domestic hot water tank k Components in domestic hot water ta...

Страница 28: ...rmostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermost...

Страница 29: ...ctrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC det...

Страница 30: ...KRTW wired room thermostat External sensor floor or ambient 2 core 4 core communication 2 core 4 core main X2M 1 4 add X2M 1a 4 main X2M 1 3 4 add X2M 1a 3 4 main X2M 1 4 add X2M 1a 4 Only for KRP1AH...

Страница 31: ...ssels pre charge pressure in domestic hot water tank kit 2 5 bar Expansion valve setting 8 bar Temperature and pressure relief valve Set opening temperature 90 95 C Set opening pressure 10 bar Replace...

Страница 32: ...4P449980 1 B 00000005 4P449980 1B 2016 11 Copyright 2016 Daikin...

Отзывы: