8 Maintenance and service

Installation manual

24

08SU EHVH08~16SU26CB6W

Daikin Altherma – Low temperature split

4P449980-1B – 2016.11

Pressure relief valve of the domestic hot water tank

Check  for  correct  operation  of  the  pressure  relief  valve  of  the
domestic  hot  water  tank.  To  ensure  free  water  flow  through  the
discharge pipe, manually operate it by turning its knob left.

Booster heater of the domestic hot water tank

It is recommended to remove lime buildup on the booster heater to
extend its life span, especially in regions with hard water. To do so,
drain  the  domestic  hot  water  tank,  remove  the  booster  heater  from
the domestic hot water tank and immerse in a bucket (or similar) with
lime-removing product for 24 hours.

Switch box

▪ Carry out a thorough visual inspection of the switch box and look

for obvious defects such as loose connections or defective wiring.

▪ Using an ohmmeter, check if contactors K1M, K2M, K3M and K5M

(depending  on  your  installation)  operate  correctly.  All  contacts  of
these  contactors  must  be  in  open  position  when  the  power  is
turned OFF.

WARNING

If  the  internal  wiring  is  damaged,  it  has  to  be  replaced  by
the  manufacturer,  its  service  agent  or  similarly  qualified
persons.

Descaling

Depending on water quality and set temperature, scale can deposit
on  the  heat  exchanger  inside  the  domestic  hot  water  tank  and  can
restrict  heat  transfer.  For  this  reason,  descaling  of  the  heat
exchanger may be required at certain intervals.

Chemical disinfection

If  the  applicable  legislation  requires  a  chemical  disinfection  in
specific situations, involving the domestic hot water tank, please be
aware  that  the  domestic  hot  water  tank  is  a  stainless  steel  cylinder
containing  an  electronic  anode.  We  recommend  to  use  a  non-
chloride based disinfectant approved for use with water intended for
human consumption.

NOTICE

When  using  means  for  descaling  or  chemical  disinfection,
it must be ensured that the water quality remains compliant
with EU directive 98/83 EC.

Anode

No maintenance or replacement required.

Pressure reducing valve of the domestic hot water tank kit

Depending  on  local  water  conditions,  annual  inspection  of  the
integral line strainer, pressure reducing valve cartridge, and seating
may be necessary.

▪ Unscrew  the  retaining  nut  of  the  valve.  The  complete  operating

mechanism, including the strainer, can be removed.

▪ Clean the filter mesh and cartridge under running water.

▪ Replace  cartridge,  ensuring  that  the  strainer  is  correctly  located,

and reassemble the unit.

Pressure relief valve of the domestic hot water tank kit

Check  for  correct  operation  of  the  pressure  relief  valve.  To  ensure
free  water  flow  through  the  discharge  pipe,  manually  operate  it  by
turning its knob left. 

Water may be very hot!

Checkpoints are:

▪ The  water  flow  coming  from  the  relief  valve  is  high  enough,  no

blockage of the valve or in between piping is suspected.

▪ Dirty water coming out of the relief valve:

▪ open the valve until the discharged water does not contain dirt

anymore

▪ flush and clean the complete tank, including the piping between

the relief valve and cold water inlet.

To make sure this water originates from the tank, check after a tank
heat  up  cycle.  It  is  recommended  to  do  this  maintenance  more
frequently.

Depending  on  local  water  conditions,  annual  inspection  of  the
pressure relief valve cartridge and seating may be necessary.

▪ Unscrew the pressure relief headwork from the valve body.

▪ Clean  the  valve  seat  face  and  seating.  Do  NOT  scratch  or

damage them.

▪ Refit in reverse order. Do NOT overtighten.

8.2.1

To drain the domestic hot water tank

Prerequisite: 

Switch OFF the power supply.

Prerequisite: 

Turn OFF the cold water supply.

1

Open the front panel.

2

Remove the 2 screws, unhook and put the switch box aside.

2

×

3

The drain hose is located at the right side of the unit. Cut the tie
wraps or tape and bring the flexible drain hose forward.

a

a

Drain hose

INFORMATION

To drain the tank, all the hot water tapping points need to
be opened to allow air to enter the system.

4

Open the drain valve.

Содержание EHVH04SU18CB6W

Страница 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHVH04SU18CB6W EHVH08SU18CB6W EHVH08SU26CB6W EHVH11SU26CB6W EHVH16SU26CB6W...

Страница 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Страница 3: ...wizard Capacities energy metering 18 5 2 5 Space heating control 18 5 2 6 Domestic hot water control 19 5 2 7 Contact helpdesk number 19 5 3 Menu structure Overview installer settings 20 6 Commission...

Страница 4: ...unit is designed for indoor installation only and for ambient temperatures ranging from 5 35 C 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tigh...

Страница 5: ...r input signal b 23 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage...

Страница 6: ...gularities The maximum allowed deviation is 1 1 NOTICE Do NOT tilt the unit backwards 0 1 1 4 3 Connecting the refrigerant piping See the outdoor unit installation manual for all guidelines specificat...

Страница 7: ...mplies with the applicable legislation INFORMATION If you have to inspect the inside of the domestic hot water tank you can access it via the booster heater boss The connection of the water piping inv...

Страница 8: ...discharge pipe and tundish are delivered with the tank kit 180 l 260 l WARNING Install the tundish away from any electrical device Possible consequence Electric shock or fire NOTICE To ensure a free...

Страница 9: ...ate the system the domestic hot water tank needs to be filled completely Turning on the system when the tank is not full can damage the integrated booster heater and cause electrical errors 4 4 6 To i...

Страница 10: ...4 5 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M 1 2 3 1 2 3 X2M X5M X6YB X6YA X6Y X1A X19A 3031 a Legend see illustration below In c...

Страница 11: ...the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax 1 Connect the backup heater power supply For 6W...

Страница 12: ...eful NOT to damage it 3 Use the 2 screws in the accessory bag to fix the wallplate of the user interface to the sheet metal of the unit Be careful NOT to distort the shape of the backside of the user...

Страница 13: ...e illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 5 10 To connect the space heating ON OFF...

Страница 14: ...red by the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the booster heater power supply and the earth cable INFORMATION The non self resetting thermal cut...

Страница 15: ...methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via t...

Страница 16: ...installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 2 Basic configuration 5 2 1 Quick wizard Lan...

Страница 17: ...ermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the unit s user interface is turned ON Code Description A...

Страница 18: ...5 Space heating control Leaving water temperature Main zone Code Description A 3 1 1 1 N A Set point mode 0 Fixed Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for...

Страница 19: ...ion on the comfort setpoint for the room Leaving water temperature Emitter type Code Description A 3 1 1 7 9 0B Reaction time of the system 0 Quick Example Small water volume and fan coils 1 Slow Exam...

Страница 20: ...heater steps Forced off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW operation Contact type main Contact type add Digi...

Страница 21: ...To check the water volume in 3 2 Preparing water piping on page 4 The domestic hot water tank is filled completely The following is properly installed see the installation manual of the domestic hot w...

Страница 22: ...o to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished...

Страница 23: ...he PCB 8 1 1 Opening the indoor unit CAUTION The front panel is heavy Be careful NOT to jam your fingers when opening or closing the unit You just need to remove the front panel of the unit to gain ac...

Страница 24: ...be ensured that the water quality remains compliant with EU directive 98 83 EC Anode No maintenance or replacement required Pressure reducing valve of the domestic hot water tank kit Depending on loc...

Страница 25: ...th drain fill valve delivered as accessory h Water filter i Space heating water IN 1 1 4 F BSP j Space heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water h...

Страница 26: ...heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water hot water OUT 3 4 F BSP m Low voltage wiring intake 24 mm n High voltage wiring intake power supply cont...

Страница 27: ...nt OUT d Plate heat exchanger e Shut off valve with drain fill valve f 3 way valve g Backup heater h Flow sensor i Pressure relief valve j Domestic hot water tank k Components in domestic hot water ta...

Страница 28: ...rmostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermost...

Страница 29: ...ctrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC det...

Страница 30: ...KRTW wired room thermostat External sensor floor or ambient 2 core 4 core communication 2 core 4 core main X2M 1 4 add X2M 1a 4 main X2M 1 3 4 add X2M 1a 3 4 main X2M 1 4 add X2M 1a 4 Only for KRP1AH...

Страница 31: ...ssels pre charge pressure in domestic hot water tank kit 2 5 bar Expansion valve setting 8 bar Temperature and pressure relief valve Set opening temperature 90 95 C Set opening pressure 10 bar Replace...

Страница 32: ...4P449980 1 B 00000005 4P449980 1B 2016 11 Copyright 2016 Daikin...

Отзывы: