background image

SVD-208-053 

 

 
2.2 Performance 

Item 

Specification 

Setting accuracy 

±1.0% (% for maximum input value) 

Repeatability 

±1.0% (% for maximum input value) 

Response time 

Operating time 

90⇔110% of step input to operation value.  Less than 300ms 

Reset time 

110⇔90% of step input to operation value.  Less than 300ms 

Influence of 
temperature 

Error of operation value:±1.0% (% for maximum input value) 

By 23±20℃ 

Error of operation time and contact delay:10.0% 

Influence of auxiliary 
supply 

Error of operation value:±1.0% (% for maximum input value) 

To auxiliary 
supply range. 

Error of operation time and contact delay:10.0% 

Influence of frequency 

Error of operation value:±1.0% (% for maximum input value) 

By 45~65Hz 

Error of operation time and contact delay:10.0% 

Influence of distorted 
wave  

Error of operation value:±1.0% (% for maximum input value) 

3rd-harmonic, 
15% mixing  

Error of operation time and contact delay:10.0% 

Overload capacity 

Voltage input 

2 times 10 seconds, 1.2 times continuation of rated voltage. 

Auxiliary supply 

1.5 times 10 seconds of rated voltage. 
Upper limit of the auxiliary supply voltage range is continued.  

Insulation resistance 

Between electric circuit and case. 

Above 50MΩ at DC500V megger. 

Between input terminals and auxiliary supply 
terminals and contact output terminals. 

Withstand voltage 

Between electric circuit and case. 

AC2000V (50/60Hz) 1 minute. 

Between input terminals and auxiliary supply 
terminals and contact output terminals. 

Impulse withstand 
voltage  

Between electric circuit and case. 

5kV 1.2/50μs.  Positive and negative 
polarity, for each 3 times. 

Between auxiliary supply terminals. 

3kV 1.2/50μs.  Positive and negative 
polarity, for each 3 times. 

Noise-capacity 

Oscillatory surge voltage 
If a vibration damping waveform (1~1.5MHz, Peak voltage : 2.5~3kV) is repeated and added,  
there is no malfunction. 
  Auxiliary supply circuit (Normal / Common) 
  AC input circuit (Normal / Common) 
  Contact output circuit (Common) 
Square wave impulse noise 
If a noise (1μs, 100ns width) is repeated and added, there is no malfunction. 
  Auxiliary supply circuit (Normal / Common)  Over 1.5kV 
  AC input circuit (Normal / Common)  Over 1.5kV 
  Contact output circuit (Common)  Over 1.0kV 
Electric wave noise  
If intermittence irradiation of the electric wave of a 150,400MHz band is done by (1W, 1m), 
there is no malfunction. 
Electrostatic noise 
±8kV (at the case of energization) is that there is no malfunction.  
±10kV (at the case of no-voltage) should not have damage or the abnormalities of parts. 

Vibration  

Malfunction:Frequency 16.7Hz, Double amplitude 1mm to X, Y, Z direction for 10 minute.  
Durability :Frequency 10~25Hz, Double amplitude 2mm to X, Y, Z direction for 2 hours. 

Shock 

Malfunction:Shock of 98m/s

2

 to X,Y,Z direction for 3 times. 

Durability :Shock of 294m/s

2

 to X,Y,Z direction for 3 times. 

 

Содержание SVD-H-105

Страница 1: ...SVD 208 053 INSTRUCTION MANUAL AC VOLTAGE ALARM SETTER SVD 105 SVD 105D With contact delay circuit...

Страница 2: ...product wet to prevent heat generation ignition product failure When this product gets wet stop using it Do not connect metal excepting wiring to terminal in order to prevent heat generation ignition...

Страница 3: ...Performance 4 2 3 Control output condition 5 3 Handling explanation 3 1 Outline dimension 6 3 2 Installation 6 3 3 Connection 7 3 4 Handling explanation 7 3 4 1 Settings 7 3 4 2 Cautions on connectio...

Страница 4: ...AC DC80 264V AC100 110V 50 60Hz AC200 220V 50 60Hz DC100 110V AC power 5 7VA DC power 2 2W DC38 58V DC48V 2 2W DC19 29V DC24V 2 2W Output Contact output Each 1c Contact capacity Maximum switching load...

Страница 5: ...voltage Between electric circuit and case AC2000V 50 60Hz 1 minute Between input terminals and auxiliary supply terminals and contact output terminals Impulse withstand voltage Between electric circu...

Страница 6: ...2 1 3 OFF L HL type Power and input conditions Drawing of input state Contact status LED indication status At contact operating ON L H Power OFF L 0 F S H 10 9 11 2 1 3 OFF OFF L H Power ON Input L L...

Страница 7: ...ation dust and corrosive gas And please select indoors without the influence of the strong electric magnetic field by the large current bus saturable reactor Please prepare the installation interval m...

Страница 8: ...tection action may be done even if it does not exceed set value They are not the abnormalities of a product 2 Variable of dead band It can do continuation variable of the dead band in dead band variab...

Страница 9: ...an accident beforehand please check an operation value periodically Caution 1 Please do not make a wiring change of the input and auxiliary supply in an energization 2 Please check a connection diagr...