background image

SVD-208-053 

 

 
1. Product outline  

This product is the setting instrument for instrumentation of the plug-in type that detects excess and deficiency 
to AC-voltage input, and outputs a contact signal.   
 

1.1 Features of product  

① This product is the high quality and high reliability and noise-proof design. 
② Detection action can be checked in a light emitting diode.  
③ The dead-band range can do variable.  
④ It can be established clearly by the digital switch. 
⑤ This product is compact plug-in type.  

 
1.2 Composition of type  

 
    S V D -   ( 1 )   - 1 0 5   ( 2 )    

 
                  (1)                                       (2) 

Mark 

Contents  

 

Mark 

Contents  

High limit setting 

- 

With no contact delay circuit  

Low limit setting 

With contact delay circuit  

HL  High and low limit setting 

 

HH  2 steps of high limit setting 
LL  2 steps of low limit setting 

 
 
2. Specification and performance 
2.1 Specification 

Item 

Specification 

Input 
(Input current) 

① 0~300V (1mA)  50/60Hz 
② 0~220V (1mA)  50/60Hz 
③ 0~173.2V [300/√

3

V] (1mA)  50/60Hz 

④ 0~150V (1mA)  50/60Hz 
⑤ 0~127V [220/√

3

V] (1mA)  50/60Hz 

⑥ 0~110V (1mA)  50/60Hz 
⑦ 0~86.6V [150/√

3

V] (1mA)  50/60Hz 

⑧ 0~63.5V [110/√

3

V] (1mA)  50/60Hz 

Auxiliary supply  

① AC・DC80~264V (AC100/110V 50/60Hz, AC200/220V 50/60Hz, DC100/110V)   
   AC power:5.7VA, DC power:2.2W 
② DC38~58V (DC48V) 2.2W 
③ DC19~29V (DC24V) 2.2W 

Output 

Contact output  Each 1c 
Contact 
capacity 

Maximum switching load:AC250V 2A (cosφ=1),DC110V 100mA (L/R=7ms) 
Minimum switching load:DC5V 10mA 

Use relay 

G6C-2114PUS (OMRON Corporation) 
Mechanical life:50 million times (Switching frequency, 300 times/minute) 
Electric life:100,000 times (Switching frequency, 30 times/minute) 

Setting range 

H :10~99% (1% step) ,L :- 

H :-                ,L :10~99% (1% step) 

HL  H :10~99% (1% step) ,L :10~99% (1% step) 
HH  H1:10~99% (1% step) ,H2:10~99% (1% step) 
LL  L1:10~99% (1% step) ,L2:10~99% (1% step) 

Dead band  

0.5~5% continuation variable  

Starting delay time(

)  0.5 second (Standard) 

(Production is possible in 0.5~10s in 0.5s step.)  

Contact delay      (

)  Option  

(Production is possible in 0.5~10s in 0.5s step.)  

Operation temperature 
and  humidity 

-10~+55℃ ,30~85% RH 

Storage temperature 

-30~+60℃ 

Case color 

Black (Munsell N1.5) 

 

Note(

) Starting delay and contact delay (option) cannot be designated simultaneously. 

[In case of starting delay designation.](TYPE:SVD-□-105) 
[In case of contact delay designation.]

(TYPE:SVD-□-105D) 

Contact delay is set to below 0.3 seconds of input-and-output response of product.  Starting delay becomes 
almost the same as the time of contact delay.  

Содержание SVD-H-105

Страница 1: ...SVD 208 053 INSTRUCTION MANUAL AC VOLTAGE ALARM SETTER SVD 105 SVD 105D With contact delay circuit...

Страница 2: ...product wet to prevent heat generation ignition product failure When this product gets wet stop using it Do not connect metal excepting wiring to terminal in order to prevent heat generation ignition...

Страница 3: ...Performance 4 2 3 Control output condition 5 3 Handling explanation 3 1 Outline dimension 6 3 2 Installation 6 3 3 Connection 7 3 4 Handling explanation 7 3 4 1 Settings 7 3 4 2 Cautions on connectio...

Страница 4: ...AC DC80 264V AC100 110V 50 60Hz AC200 220V 50 60Hz DC100 110V AC power 5 7VA DC power 2 2W DC38 58V DC48V 2 2W DC19 29V DC24V 2 2W Output Contact output Each 1c Contact capacity Maximum switching load...

Страница 5: ...voltage Between electric circuit and case AC2000V 50 60Hz 1 minute Between input terminals and auxiliary supply terminals and contact output terminals Impulse withstand voltage Between electric circu...

Страница 6: ...2 1 3 OFF L HL type Power and input conditions Drawing of input state Contact status LED indication status At contact operating ON L H Power OFF L 0 F S H 10 9 11 2 1 3 OFF OFF L H Power ON Input L L...

Страница 7: ...ation dust and corrosive gas And please select indoors without the influence of the strong electric magnetic field by the large current bus saturable reactor Please prepare the installation interval m...

Страница 8: ...tection action may be done even if it does not exceed set value They are not the abnormalities of a product 2 Variable of dead band It can do continuation variable of the dead band in dead band variab...

Страница 9: ...an accident beforehand please check an operation value periodically Caution 1 Please do not make a wiring change of the input and auxiliary supply in an energization 2 Please check a connection diagr...

Отзывы: