SVD-208-053 

 

 
3.3 Connection 

             

 

TYPE 

Contact 

HH 

H1 

H2 

LL 

L2 

L1 

HL 

- 

- 

 
3.4 Handling explanation  

The usage of this product should check the name plate and specification of actual goods, and should perform the 
right handling. 

 
3.4.1 Settings 

(1)

 

The setup of operation value.  
Please set to needed operation value in a front digital switch.  
It can set to 10~99% (1% step), using rated voltage as 100%.  
 
<Caution> If a digital switch is set in the state of power-supply applying, detection action may be done even 

if it does not exceed set value. (They are not the abnormalities of a product.) 

 

(2)

 

Variable of dead band. 
It can do continuation variable of the dead band in dead-band variable VR.  0.5~5% 

 
3.4.2 Cautions on connections 

(1)

 

An external connection terminal is M3.5 screw terminal.  Please use a solderless contact for connection with 
a terminal.   
The tightening torque of a screw is 0.7~0.9N・m(7.1~9.2kg・cm) 

 

(2)

 

In case inductive loads, such as an electromagnetic relay, are connected to contact output, we recommend you 
to install a diode, a surge killer, etc. near load like the example of the following figure.  

 

《 An example of a spark elimination circuit 》 

 

R

C

 

 
 

Содержание SVD-H-105

Страница 1: ...SVD 208 053 INSTRUCTION MANUAL AC VOLTAGE ALARM SETTER SVD 105 SVD 105D With contact delay circuit...

Страница 2: ...product wet to prevent heat generation ignition product failure When this product gets wet stop using it Do not connect metal excepting wiring to terminal in order to prevent heat generation ignition...

Страница 3: ...Performance 4 2 3 Control output condition 5 3 Handling explanation 3 1 Outline dimension 6 3 2 Installation 6 3 3 Connection 7 3 4 Handling explanation 7 3 4 1 Settings 7 3 4 2 Cautions on connectio...

Страница 4: ...AC DC80 264V AC100 110V 50 60Hz AC200 220V 50 60Hz DC100 110V AC power 5 7VA DC power 2 2W DC38 58V DC48V 2 2W DC19 29V DC24V 2 2W Output Contact output Each 1c Contact capacity Maximum switching load...

Страница 5: ...voltage Between electric circuit and case AC2000V 50 60Hz 1 minute Between input terminals and auxiliary supply terminals and contact output terminals Impulse withstand voltage Between electric circu...

Страница 6: ...2 1 3 OFF L HL type Power and input conditions Drawing of input state Contact status LED indication status At contact operating ON L H Power OFF L 0 F S H 10 9 11 2 1 3 OFF OFF L H Power ON Input L L...

Страница 7: ...ation dust and corrosive gas And please select indoors without the influence of the strong electric magnetic field by the large current bus saturable reactor Please prepare the installation interval m...

Страница 8: ...tection action may be done even if it does not exceed set value They are not the abnormalities of a product 2 Variable of dead band It can do continuation variable of the dead band in dead band variab...

Страница 9: ...an accident beforehand please check an operation value periodically Caution 1 Please do not make a wiring change of the input and auxiliary supply in an energization 2 Please check a connection diagr...

Отзывы: