background image

6

Installation Specifications

Planning the Installation

General System Layout

The vent system consists of the downdraft vent and a 

Dacor-approved cabinet blower (MRV3015 and MRV3615), 

remote blower, or in-line blower. (See Pg. 7).

 WARNING

• Failure to install an approved blower and proper duct-

ing will cause a backdraft and poor venting.

• To reduce risk of personal injury from reaching over a

hot appliance, avoid cabinet storage directly above the

cooking surface.

• Follow minimum clearances and installation location in

the vent, appliance, and blower instructions. Failure to

do so may cause a fire or safety hazard.

• Plan the installation so minimum dimensions are met or

exceeded. All contact surfaces between the downdraft

vent and cabinets/walls must be solid and at right angles.

• The downdraft vent has adjustable anchor legs to accom-

modate various cabinet heights.

• Install the downdraft vent and range/cooktop so they can

be removed for service.

• Allow access from the cabinet front to the chassis, and

utilities of the downdraft vent and cooktop for inspection

and service. (Drawers/shelves must be removable.)

• There are 7/8” access holes in the bottom and side of the

downdraft vent for connecting blower wiring and strain

relief. Wire the blower to turn on when the downdraft vent

is turned on. When installing a remote or in-line blower,

run the blower wiring/conduit parallel to the duct work,

connecting it to the downdraft vent on one end and the

blower on the other.

• Allow room for the exhaust duct coming out of the unit.

(See 

Planning the Duct Work

, Pg. 8, for details.)

• Consider the maximum-allowable duct run when decid-

ing the layout. (See 

Planning the Duct Work

, Pg. 8, for

details.)

• See the range/cooktop installation instructions for mini-

mum cutout dimensions specific to the downdraft vent

being installed.

Vertical

non-combustible

surface rear wall

Notches for self-rimming

style installations, see range 

installation instructions

Notches required for some downdraft vent

installations, see range 

installation instructions

Backsplash

Countertop

overhang

See the range installation 

instructions for exact countertop 

and cabinet dimensions

Vertical

non-combustible

surface rear wall

Notches required for some downdraft vent

installations, see cooktop 

installation instructions

Backsplash

Countertop

overhang

See the cooktop installation 

instructions for exact countertop 

and cabinet dimensions

Flush with back side

of cabinet front

Range Cabinet/Countertop Cutout - Top View

Cooktop Cabinet/Countertop Cutout - Top View

Содержание HRV46

Страница 1: ...RV48 ER Includes installation instructions for Dacor cabinet blower CABP3 which is an option for the indicated models Part No 113910 Rev E Use these downdraft vents only with approved Dacor appliances...

Страница 2: ...nd the local electrical inspector s use Customer Assurance Information All specifications subject to change without notice Dacor assumes no liability for such changes 2018 Dacor all rights reserved Mo...

Страница 3: ...an outlet is available for the appliance Do not remove the third ground prong from the power cord use an adapter plug use an extension cord use a damaged power cord Use a ground fault interrupter GFI...

Страница 4: ...s become blocked Do not let foreign objects be sucked into vent holes Clean the filters and all grease laden surfaces often to pre vent grease fires and maintain performance Clean the appli ance only...

Страница 5: ...for exhaust locations and dimensions Maximum height of downdraft vent must not exceed maximum specified counter height for cooking appliance See installation instructions for cooking appliance Total c...

Страница 6: ...down Tolerances 1 16 1 6 mm unless otherwise stated See Pg 9 for exhaust locations dimensions Max height of downdraft must not exceed cooking unit s max specified counter height See cooking unit s ins...

Страница 7: ...ust locations dimensions Max height of downdraft vent must not exceed cooking appliance s max specified counter height See cooking appliance s installation instructions IMPORTANT INSTALLER To ensure t...

Страница 8: ...f the downdraft vent for connecting blower wiring and strain relief Wire the blower to turn on when the downdraft vent is turned on When installing a remote or in line blower run the blower wiring con...

Страница 9: ...de wall Downdraft vent Downdraft vent configured for bottom exhaust Floor Wiring conduit from downdraft to in line blower Cabinet back Front of unit Connection to cabinet blower Blower wiring access h...

Страница 10: ...raft vent s air draw Building codes may require makeup air systems with ven tilation systems that move air greater than the specified movement rate CFM Consult a qualified HVAC specialist when designi...

Страница 11: ...ne of bottom knock out lines up with vertical center line of chassis On 30 and 36 wide models the vertical center line of bottom knock out is offset 3 Side Exhaust Knock Outs 1 5 8 x 16 Bottom Exhaust...

Страница 12: ...onnection center line A Downdraft vent center line Countertop 3 1 4 x 10 duct connection 26 1 4 66 7 cm Exhaust Locations and Side Dimensions for CABP3 Cabinet blower Front Exhaust Dimensions CABP3 Bl...

Страница 13: ...e above parts is 15 ft 15 ft 4 ft 2 ft 36 ft The max amount of straight duct that can be used with a REMP16 and the above parts is 60 ft 34 ft 24 ft Equivalent Number of Feet Nominal Duct Elbows and T...

Страница 14: ...cooktop Install the down draft vent before installing the range or cooktop 2 Start by loosely attaching the anchoring legs to the studs on the left and right sides of the downdraft vent using the prov...

Страница 15: ...ard the 3 lock washers which will be replaced Tilt the cover out and pull up to remove it 2 Peel the backing off of some of the foam tape included with the adapter Attach it to the right and left flan...

Страница 16: ...o right left flanges Adapter New label Existing label ILHSF or REMP Series Blower Installation If using a ILHSF or REMP series blower install it according to the blower installation instructions Duct...

Страница 17: ...cal Installation CABP3 Cabinet Blower Downdraft Vent Electrical Access Panel Front of unit Wire Colors Black Line L White Neutral N Green Ground Gnd Electrical connection from downdraft vent match Wir...

Страница 18: ...aft vent Ensure the downdraft vent supplies power to the blower If the vent will not raise properly or makes a scraping sound check for under counter obstructions If the downdraft vent fails to functi...

Страница 19: ...LK WHT WHT Wiring Diagram All Models CABP3 Cabinet Blower Ratings CABP3 Cabinet blower Airflow Nominal 600 CFM Actual 585 6 CFM At zero inches static pressure Performance varies based on duct system c...

Страница 20: ...Dacor 14425 Clark Avenue City of Industry CA 91745 Phone 800 793 0093 Fax 626 403 3130 www dacor com...

Отзывы: