Gas Requirements
Provide Adequate Gas Supply
•
Installation must follow local codes or, in their absence, the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
•
The cooktop operates at a manifold pressure of 5 in. (13 cm) of water column for natural gas/natural gas at
high altitude (NG-H) or 10 in. (25.4 cm) of water column for LP (propane)/LP at high altitude (LP-H).
• Verify that the oven is right for the provided gas service. When verifying regulator function, inlet pressure
must be at least 1 in. (2.5 cm) greater than the operating (manifold) pressure as given.
•
The regulator inlet receives a 3/4” gas line. (The range ships with a 1/2”-to-3/4” adapter on the regulator.)
•
The figures in the table at
right are for reference only.
(See the rating label—rear
top-right corner of range—
for exact measurements.)
Installation Requirements
Special Gas Requirements (gas models sold in Massachusetts)
•
Gas suppliers recommend installing a UL-approved gas detector per manufacturer specifications.
•
The range must be installed by a plumber or gas fitter certified by the State of Massachusetts.
• A T-handle, manual gas valve must be installed in the gas-supply line to the range.
•
If using a flexible gas connector, multiple lines must not be connected in series.
• The pressure regulator at
the inlet of the cooktop
manifold must stay in the supply line no matter the type of gas used.
•
Use only the range's regulator, which must be installed in the line between the cooktop gas inlet and the
shut-off valve.
•
An external, manual shut-off valve must be installed between the gas inlet and the range.
•
Ensure the connectors are installed by a qualified installer.
•
For safety’s sake, use only new flexible connectors.
MINIMUM GAS-SUPPLY PRESSURE REQUIREMENTS*
Gas Type
Min. Manifold Pressure
Min. Gas-Supply Pressure**
Natural gas
5” water column
6” water column
LP (propane) gas
10” water column
11” water column
*Gas-supply pressure for testing the regulator setting shall be at least 1” water column (249
Pa) above the specified manifold pressure; **Max gas-supply pressure, all models: 1/2 psi.