17
* Note) In Function mode, if the value of F-13 is set the Base Offset (page26) , the
comparative output operates as follows.
1) Decision mode :
Measured Value
≤
(Offset-Lower limit setup value)
⇒
RY1 ON (Low)
Measured Value
≥
(Upper limit setup value)
⇒
RY3 ON (Hi)
(Offset -
Lower limit setup value) < Measured value < (Upper limit setup value)
⇒
RY2 ON (OK)
2) High limit mode : Measured Value
≥
(RY1 setup value)
⇒
RY1 ON
Measured Value
≥
(RY2 setup value)
⇒
RY2 ON
Measured Value
≥
(RY3 setup value)
⇒
RY3 ON
Measured Value
≥
(RY4 setup value)
⇒
RY4 ON
Measured Value <( RY1 setup value) – Hysteresis value
⇒
RY1 OFF
Measured Value< (RY2 setup value) - Hysteresis value
⇒
RY2 OFF
Measured Value < (RY3 setup value) – Hysteresis value
⇒
RY3 OFF
Measured Value< (RY4 setup value) - Hysteresis value
⇒
RY4OFF
3) Low limit mode :
Measured Value
≤
(RY1 setup value)
⇒
RY1 ON
Measured Value
≤
(RY2 setup value)
⇒
RY2 ON
Measured Value
≤
(RY3 setup value)
⇒
RY3 ON
Measured Value
≤
(RY4 setup value)
⇒
RY4 ON
Measured Value > (RY1 setup value) + Hysteresis value
⇒
RY1 OFF
Measured Value > (RY2 setup value) + Hysteresis value
⇒
RY2 OFF
Measured Value > (RY3 setup value) + Hysteresis value
⇒
RY3 OFF
Measured Value > (RY4 setup value) + Hysteresis value
⇒
RY4 OFF
4) Low & High limit mode
Measured Value
≤
(RY1 setup value)
⇒
RY1 ON
Measured Value
≤
(RY2 setup value)
⇒
RY2 ON
Measured Value
≥
(RY3 setup value)
⇒
RY3 ON
Measured Value
≥
(RY4 setup value)
⇒
RY4 ON
Measured Value > (RY1 setup value) + Hysteresis value
⇒
RY1 OFF
Measured Value > (RY2 setup value )+ Hysteresis value
⇒
RY2 OFF
Measured Value <( RY3 setup value) - Hysteresis value
⇒
RY3 OFF
Measured Value < (RY4 setup value) - Hysteresis value
⇒
RY4 OFF