7.

Auxiliary Light

The Auxiliary Light output is 

used to connect an external light 

to the operator. The external 

light can be switched on when 

the operator is triggered for a 

preselected period of  me (up 

to 9 minutes) or the light can be 

ac vated via a dedicated remote 

bu on, without triggering the 

operator. If switched on by a 

dedicated bu on, it will remain 

on for a period of 1 hour but can 

be switched off before 1 hour is 

up by pressing the same bu on 

again. 

Refer to ‘Se ng Auxiliary 

Output....Menu 5’ for 

programming.

LUX DC12

Control Board

NO

COM

DACE

Relay Module

Code: SA001

N

L

External 

Light

 

CONNECTING A SOLAR PANEL

Solar panels must be mounted in direct sunlight and the 

panel angle alignment should be adjusted for op mal 

condi ons for the loca on. It is very important to ensure 

that no shadows will cross the panel during the day. 

It is recommended that a ba ery with a capacity of at least 

7Ah

 is used. 

The operator will automa cally detect that it is connected 

to a solar supply once the panel voltage exceeds 17V DC. It 

will then no longer indicate a power fail message but will 

only display a single bar "_" when the panel output voltage 

is too low for charging. 

When connec ng a solar panel directly to the controller 

the transformer must be removed from the input.
Solar Panel specs: 

Power Ra ng:

 

20W min

Min Voltage output:

 

17V DC

Max Voltage Output:

 

22V DC.

REV

AUX LOCK

12V   TRIG   INF   GND 

Power

Input

REV

LIMITS

AUX LOCK 12V TRIG INF GND 

Power

Input

LUX DC12 Control Board

Not Polarity

Sensi ve

Solar Panel

ERROR CODES

ERROR 

CODE

MEANING

CAUSE & REMEDY

Lb

Low Ba ery

Cause

:

Low ba ery voltage. The ba ery may be faulty or an excessive number of 

opera ons, or devices, may have drained the ba ery.

Remedy

:

Ensure the operator is plugged in and switched on. Fully charging a 5Ah 12V 

ba ery will take 24hrs if the operator is not in use and if no other devices, such as 

locks; receivers & lights, are connected.

Check that connected devices are not drawing excessive currents.

Addi onal devices will reduce the number of daily opera ons and standby 

opera ons.

PF

Power Fail

Cause

:

The operator is not detec ng an input supply voltage.

Remedy

:

If using a transformer, ensure that the transformer is plugged in and switched on. 

The output voltage should be between 12VAC – 18VAC, if not the transformer may 

need to be replaced.

If using a solar panel, ensure the output voltage is between 17VDC - 22VDC. When 

a solar panel is connected to the operator it is necessary for the DC voltage to be 

higher than 17V for the operator to switch to DC Solar Opera on a er which the 

operator will stop showing the Power Fail message.

Thank you for choosing Dura Access Control Equipment (DACE). We welcome you to the ever growing interna onal 

community of  DACE product owners. The advanced engineering and high-quality construc on of each DACE 

product we build is something of which we are proud.

 

The LUX DC12 garage operator is packed with features to bring you convenience and enhance your security.

 

Your owners manual will introduce you to the features and opera on of your new LUX DC12. It is suggested that 

you read it carefully since the informa on it contains can contribute greatly to the sa sfac on you receive from 

your new garage door operator.

 

Only automate garage doors that are within specifica on and are in good working order. The door must be able 

to be opened and closed using only one hand and, if released midway, the door should not move. The force 

used to open the door by hand should be similar to that used to close the door. If the door is not in perfect 

working order, it should be serviced by a qualified garage door technician prior to automa on.

Automa ng a garage door increases the risk of entrapment and crushing. While all reasonable steps have been 

taken to ensure that your garage door operator is safe to install and operate, it must be noted that a garage 

door is a heavy piece of equipment and can cause serious injury and death. Never allow children to play with or 

around the garage door. Only ac vate the garage door when it is in full view and when there are no children or 

animals in close proximity that could get injured.

We highly recommend the installa on of Infrared Safety Beams to increase the safety of the doors opera on.

The LUX DC12 is not waterproof and is therefore not suitable for outdoor use.

It is important to note that the LUX DC12 garage operator is ba ery operated and by simply switching off the 

mains power supply to the operator it does not mean that the operator does not have power. It is therefore 

important that both the mains power supply and the ba ery be disconnected before working on the operator.

Use extreme cau on when opera ng the manual release as the door may move, resul ng in injury or damage. 

The door should be inspected every 6 months by disengaging it from the operator and moving it by hand. The 

door should move easily but it should not close on its own if released. If the door is found to be defec ve, it 

must remain disconnected from the operator and a qualified garage door technician be called to carry out 

repairs to the door.

Please a ach your invoice to this manual for future use (see warranty)

FOREWORD

 

Important informa on before automa ng your garage door!

3

DISCLAIMER

Dura Access Control Equipment reserves the right to make changes to the products described in this manual  

without no ce and without obliga on to no fy any persons or organisa ons of such revisions or changes. 

Addi onally, DACE makes no representa ons or warran es with respect to this manual. 

This manual may only be copied or distributed as a whole, no altera ons or subsec ons may be distributed or 

copied without the prior express consent of DACE in wri ng

Содержание LUX DC12

Страница 1: ...the operator such as a transformer ba ery or beams warranty informa on regarding products may be found in the installa on guide pertaining to each product This warranty explicitly only covers the repa...

Страница 2: ...wo of the remote bu ons simultaneously This will reduce the risk of accidentally ac va ng the Lockout func on ES Encoder Stop Fault Obstruc on Cause The operator has stalled This could be as a result...

Страница 3: ...ers The advanced engineering and high quality construc on of each DACE product we build is something of which we are proud The LUX DC12 garage operator is packed with features to bring you convenience...

Страница 4: ...energy instead of a buildings mains supply for charging the operator s ba ery Transformer An external device connected to the buildings mains supply via a plug point that reduces the mains voltage to...

Страница 5: ...Board DuraOp cs Wireless Safety Beams REV LIMITS AUX LOCK 12V TRIG INF GND NO GND COM 12V 24V NC FET Power Input Cau on When ng a Magne c Lock to the door no NOT use the power from the operator as th...

Страница 6: ...AYOUT CONTROL BOARD LAYOUT REV LIMITS AUX LOCK 12V TRIG INF GND Inputs Outputs Power Input 12 18V AC or 17 22V DC Solar ve ve Ba ery Cables Motor Wire Red Motor Wire Black Blue 20A Fuse Motor DBUS Inp...

Страница 7: ...you to the Programming Menu Pr R c SET p r SET b c SET L E 18 L o SET 1 Ensure the ba ery is connected to the Operator 2 Press the SET bu on to enter the Programming Menu Pr 3 Press the DOWN bu on un...

Страница 8: ...5 Press the DOWN bu on un l Lt Light is visible 6 Press and hold the remote bu on that is to be used to turn the operator light on and o Do not use the same bu on that was programmed to trigger the op...

Страница 9: ...enu Pr 3 Press the DOWN bu on un l the Remote Menu rc is visible 4 Press the SET bu on to enter the Remote Menu The display will change to LE Learn 5 To program a remote press and hold the remote bu o...

Страница 10: ...hts or bypass alarm passives when entering the garage Press the SET bu on to enter the AL menu Press the UP or DOWN bu ons to scroll through the me op ons T0 to T9 Press the SET bu on to select the de...

Страница 11: ...re is free movement of the Li ing Assembly on the Drive Channel Li the door s manually to various heights and ensure that the door s do not close under their own weight If they do then it will be nece...

Страница 12: ...ng the door will stop brie y and then reopen to the fully open posi on If the door is opening and it is stopped within 30cm of the fully closed posi on it will con nue opening when it receives the nex...

Отзывы: