ENGLISH
19
Figure 5: Input Status Page
2.8
Output contacts
The connections of the outputs listed below refer to the terminal board indicated with screen printing O1, O2 and CA.
Table 3 describes the characteristics and limits of the output contacts.
Characteristics of the output contacts
Type of contact
NO (Normally open)
Max. bearable voltage [V]
230 VAC
Max. bearable current [A]
5 -> resistive load
2.5 -> inductive load
Max. accepted cable section [mm²]
2.5
Table 4: Characteristics of the output contacts
The correspondences between relays and outputs are described below:
Label
Corresponding Output
RL6
O1
RL7
O2
RL8
O3
RL9
O4
Table 5: Relay Output correspondence
An example of a connection is shown below, on output O1 with a 230V load.