ENGLISH
31
8.8
Troubleshooting ES 1 M – ES 3 M
FAULTS CHECK
(POSSIBLE
CAUSES)
REMEDY
1.
The motor is not
fed
A.
The protection of the control BOX or the
differential automatic switch on the
distribution panel has tripped.
B.
No voltage on terminals L1-N
C.
The protection of the internal transformer has
tripped.
D.
The remote control switch ref. KM1 vibrates.
E.
Check the connection of input B on the panel
and any pressure switch, level switch or other
device.
A.
Check the insulation of the pump cables. Reset
the la protection of the control BOX or the
differential switch on the distribution panel.
B.
Check the panel connecting cables and any
switches or insulating switches that may have
tripped in the system.
C.
Turn off the main switch for three minutes, then
switch it on again Starting of the electropump
excludes the fault. If the electropump is not fed,
or is temporarily fed, identify any short circuits
in the secondary circuit of the transformer.
D.
The supply voltage is insufficient.
E.
Remove the fault in the electric connections .
2.
The protection of
the control BOX
intervenes.
A.
Pump impeller blocked.
B.
The motor absorption is excessive at full
load.
C.
The overload protection is faulty
A.
Carry out maintenance to free the impeller.
B.
During operation the line voltage is outside the
/- 10% of the rated voltage; or carry out
maintenance on the electropump (check the
state of the bearings)
C.
Change the component or the control unit.
3.
The pump does
not deliver, the
motor does not
start, the lamp
HL2 is lit, the
lamp HL3 is off
A.
The electro-probe circuit is not efficient; the
resistance between the electro-probe lead and
the earth terminal must be < 80 k ohm
B.
The electro-probe is not immersed in the
water.
C.
The input remote control circuit at terminals
B is open.
D.
The microswitch SP1 is not correctly
positioned.
E.
The module M2S is faulty.
A.
Change the connections of the electro-probe or
the electro-probe itself. Insert the common
electro-probe connected to terminal 18 ref. I if
the water is not directly in contact with the
earth system.
B.
Position the electro-probe under the water level.
C.
Close the contacts of the input remote control
circuit at terminals B, check efficiency of the
pressure switch, level switch or other device.
D.
Position the microswitch SP1 depending on the
number of the electro-probes to be used.
E.
Replace the Module M2S.
4.
The pump
continues
delivering and
does not respond
to external
commands
A.
The pressure switch, level switch or other
device is not correctly connected to the
control unit.
A.
Correctly connect the pressure switch, level
switch or other device and check system
operation. If necessary, change the component..
5.
The remote
alarm is not
working
A.
The connections do not correspond to the
diagram proposed.
B.
The acoustic or luminous warnings are not
efficient.
A.
Make the connections following the diagram
proposed.
B.
Change the component.
8.9 List of spare parts
ES 1 M
REF
Code Description
Model
QM1 002740051 MODULAR
AUTOMATIC
SWITCH
1P+N 10A
19133 MERLIN GERIN
EF 681 0 ABB
LN C10 SIEI
KM1
002773460
REMOTE CONTROL SWITCH 4KW 400V AC3 24V 50/60Hz
LC1 D09 B7 TELEMECANIQUE
100-C09KJ10 AB
A 09-30-10 ABB
TC1
002771290
SINGLE-PHASE TRANSFORMER 0-230/24 30VA
BL1 002776190 PROBES
MODULE
ES 3 M
REF
Code Description
Model
QM1 002740052 MODULAR
AUTOMATIC
SWITCH
1P+N 16°
19135 MERLIN GERIN
EF 682 8 ABB
LNC 16 SIEI
KM1
002773465
REMOTE CONTROL SWITCH 7.5KW 400V AC3 24V 50/60Hz
LC1 D18 B7 TELEMECANIQUE
100-C16KJ10 AB
A 16-30-10 ABB
TC1
002771290
SINGLE-PHASE TRANSFORMER 0-230/24 30VA
BL1 002776190 PROBES
MODULE