Intended use
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 24 VDC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
99.824.31 1.2/03/12
ZA-BSY+
6/20
English
Performance features
-
icroprocessor controlled synchro electronics
BSY + for a precise synchronous run of up to
8 drives
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
-
specially silent in ventilation operation
because of reduced motor speed
M
E
-
ndividually programmable (via software SW-BSY+)
I
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Extent of supply
Pressure load diagram
500
600
800
1000
1
100
1200
1300
1400
1500
1600
0
200
400
600
800
1000
1200
1400
max.
Load
(N)
Stroke (mm)
Permanent
Temporary
Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.
Mounting informations
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged
- Drives with a stroke of
must not be moun-
ted „hung up at the bottom“ (e.g. bracket UK)
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
≥
800 mm
- The drive set will be full configured by factory.
The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SW-BSY+
- Use only drives with the same force.
- Ensure evenly load distribution on all the drives
Safety notes
Operating voltage 24 VDC!
Observe enclosed red safety slip!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the toothed rack!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Use option “-W“ in case of outside mounting!
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!