99.824.29 1.2/03/12
5/16
ZA 35/85/105/155
English
Safety notes
Intended use
Performance features
Scope of supply
Pressure load diagram
500
600
800
1000
1
100
1200
1300
1400
1500
1600
0
200
400
600
800
1000
1200
1400
max.
Load
(N)
Stroke (mm)
Permanent
Temporary
Mounting informations
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 24 VDC
-
seable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
U
-
icroprocessor controlled electronics
-
djusting of stroke with PLP1 directly at the drive
via Powerline (PLP1
and PDA service tool)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
-
specially silent in ventilation operation
because of reduced motor speed
-
able entry interchangeable from the bottom
to the top
M
A
E
C
-
ndividually programmable
I
Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.
Operating voltage 24 VDC!
Observe enclosed red safety slip!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the toothed rack!
- Use only in dry rooms
- Only for inside mounting
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Use option “-W“ in case of outside mounting!
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged
- Drives with a stroke of
must not be moun-
ted „hung up at the bottom“ (e.g. bracket UK)
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
- Technical clarification is required with D+H in case
of only tensile force applications of more than 500N
800 mm
- A programming should be done before
installation, because the drives can only be
programmed individually connected
- ZA-TM drives may not be connected with a
coupling shaft (VW).
A combination with a slave unit (ZM) is permitted
ZA-TM
ZA-TM
ZM
ZA-TM
VW