Guarantee
Maintenance
Smoke and heat vent systems must be maintained
at annual intervals by authorized specialist
companies according to DIN 18232 section 2
paragraph 10.2, and VDE 0833 section 1
paragraph 5.3.4 for alarm systems and
manufacturer guidelines.
Renew test badge, keep control book.
The respective current D+H maintenance
instruction is decisive.
D+H authorized expert companies have been
specially trained by D+H for carrying out expertly
this maintenance, and they get automatically the
latest maintenance instructions.
Following tests must be carried out in the course of
maintenance:
- Outside examination/ inspection of system
components
- Measuring of insulation resistances
- Checking of all relevant power supply units
- Functional testing of connected system
components
- Record of competent carrying-out of
maintenance, and designation according
to directions
Once a year by a specialist company, who is
authorized by the appliance manufacturer.
Only regular and professional maintenance
warrants the necessary and permanent
functional safety.
Only authorized specialist companies are allowed
to install and maintain smoke and heat vent
systems and system components, constructed and
distributed by
. All
partners belong to these
authorized specialist companies, who regularly
undergo an in-house training to ensure their
qualification and experience.
According to DIN VDE 0108 section 1 paragraph
9.1.1 accumulators for emergency supply (lead
accumulators) must be checked every six months
by a person, who has been introduced to this task,
and once a year, maintenance must be carried out
by specialist companies.
Accumulator types, which are used for
smoke and heat vent systems
must be VdS approved, and must be released by
to use in smoke and heat
vent systems.
According to DIN 18232 section 2 paragraph 10.2
the tests must be put down in an operational book,
which the operator/ building owner must present to
the building supervision authority on request.
This operational book is available at
(Ord.-No.: 68.700.15)
Executed maintenance must be proved by a
maintenance/ and testing
confirmation.
Observe regulations for danger warning systems
VDE 0833, guidelines for electrical systems VdS
2221, DIN 18232 for smoke and heat vent systems,
regulations of the local fire-brigade and of EVU for
connection to mains supply.
D+H Mechatronic AG
D+H
Mechatronic AG
D+H
Mechatronic AG
D+H Mechatronic AG
D+H
Mechatronic AG
D+H
Mechatronic AG
You will get
guarantee for all D+H products
from date of verified handing over of the system up
to maximal 3 years after date of delivery, when
mounting and starting has been carried out by a
D+H authorized
.
2 years
distributor
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.