5.8
1 2 3 4
ON SAB
1 2 3 4
ON SAB
1 2 3 4 5 6 7 8
ON
SAB
1 2 3 4 5 6 7 8
ON
SAB
30/48
LSC 44-M4
99.823.35 1.2/06/09
Codification of Line 1 and 2
Switch 1 on ON =
Two-smoke detectors dependency
Attention!
Switch
Smoke detector alarm can be reset only in control panel
Dip switch 2 must be switched on OFF, when remote reset is desired of smoke detectors by the
smoke vent button.
Switch
Switch
Alarm will be triggered only, if at least two smoke detectors of one line respond.
False alarm of one smoke detector will be prevented.
Two smoke detectors in one room must be always installed.
If only one smoke detector is connected to one line, switch is on OFF!
Smoke detector alarm can
be reset by single pressing on button in smoke
vent button.
(Only in conjunction with FO 1362)
See also page 18 about this.
2 on ON
=
3 on ON
= Line fault = alarm
smoke vent opens
line fault
4
=
The control panel will be switched on alarm, that means the
at a
(e.g. at an interrupted detector line or short circuit).
idle
not
Following functionings can be set with
on motherboard.
DIP switch S1/ S3
Line 1
Line 2