Mounting height
Fastening
Housing colour
1.5m above upper edge of flooring.
With plug screws 4,5x40mm diogonal or direct on
55m flush socket with 2 screws.
Standard:
deep orange (RAL 2011) according to VdS 2592.
However, locally variant, other colours can be
demanded.
Please consult your D+H partner.
Technical Data
Voltage
:
24V ±4V
Alarm circuit
:
20 mA
Temperature range :
-5°C to +40°C
green
red
yellow *
system is
operable
meaning
alarm
malfunction
Mounting
Connection
LED
lightens
LED
flashes
Smoke vent button RT 43-H-LSC
Application
Smoke vent button
RT 43-H-LSC
alarm
control
line
line
malfunction
closed