Chapter 3 LCD Panel
40
SM 180-600 KMFX User Manual
Submenu
Name
Contents
Meaning
Date&Time
Date format setting
Three formats: (a) year/month/day, (b)
month/date/year
,
(c) date/month/year
Time setting
Setting time
Language
Current language
Language in use
Language selection
Simplified Chinese and English selectable
(
The setting taking action immediately
after touching the language icon
)
COMM.
Device Address
Setting the communication address
RS232 Protocol Selection
SNT Protocol, ModBus Protocol, YD/T
Protocol and Dwin
(
For factory use
)
Baudrate
Setting the baudrate of SNT, ModBus and
YD/T
Modbus Mode
Setting mode for Modbus:ASCII and RTU
selectable
Modbus parity
Setting the parity for Modbus
USER
Output voltage Adjustment
Setting the Output Voltage
Bypass Voltage Up Limited
Up limited working Voltage for Bypass
,
se10%
,
+15%
,
+20%
,
+25%
Bypass
Voltage
Down
Limited
Down limited working Voltage for Bypass
,
settable:-10%
,
-15%
,
-20%
,
-30%
,
-40%
Bypass Frequency Limited
Permitted working Frequency for Bypass
Settable
:
+-1Hz
,
+-3Hz
,
+-5Hz
Dust Filter Maintenance
Period
Setting Dust Filter Maintenance Period
BATTERY
Battery Number
Setting the number of the battery
(
12V
)
Battery Capacity
Setting of the AH of the battery
Float Charge Voltage/Cell
Setting the floating Voltage for battery cell
(
2V
)
Boost Charge Voltage/Cell
Setting the boost Voltage for battery cell
(
2V
)
EOD(End of discharge)
Voltage/Cell,@0.6C
Current
EOD voltage for cell battery,@0.6C current
EOD(End
of
charge)
Voltage/Cell,@0.15C
Current
EOD voltage for cell battery,@0.15C
current
Charge
Current
Percent
Limit
Charge current (percentage of the rated
current)
Battery
Temperature
Compensate
Coefficient
for
battery
temperature
compensation
Boost Charge Time Limit
Setting boost charging time
Auto Boost Period
Setting the auto boost period
Auto
Maintenance
Discharge Period
Setting the period for auto maintenance
discharge
SERVICE
System Mode
Setting the system mode: Single , parallel,