REPLACING THE BATTERY
(
only OM1500ATLCD
)
Replacement of batteries located in an
OPERATOR ACCESS AREA.
1. When replacing batteries, replace with the same number of the following battery: Cyberpower /
RBP0089for the OM1500ATLCD.
2.
CAUTION!
Risk of Energy Hazard, 12V, maximum 7.5Ampere-hour battery. Before replacing
batteries, remove conductive jewelry such as chains, wrist watches, and rings. High energy
conducted through these materials could cause severe burns.
3.
CAUTION!
Do not dispose of batteries in a fire. The batteries may explode.
4.
CAUTION!
Do not open or mutilate batteries. Released material is harmful to the skin and eyes.
It may be toxic.
5.
CAUTION!
A battery can present a risk of electrical shock and high short circuit current. The
following precautions should be observed when working on batteries:
1) Remove watches rings, or other metal objects.
2) Use tools with insulated handles.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE
OF USED BATTERIES ACCORDING TO LOCAL REGULATIONS.
BATTERY REPLACEMENT PROCEDURE
1.
Turn off and unplug all connected equipment.
2.
Turn the UPS off and unplug it from the AC power source.
3.
Turn the UPS on its side.
4.
Remove the screws on the bottom of the front panel and lay aside.
5.
Remove the front panel of the UPS: pull and lift it.
6.
Take out the battery compartment cover.
7.
Disconnect the battery wires from the battery.
8.
Remove the battery from the compartment.
9.
Put the battery back into the compartment.
10. Install the replacement battery by connecting the red wire (+) and black wire (-) to the same color
connectors from the battery pack.
11. Replace the battery compartment cover.
12. Align the front panel and tighten the retaining screws.
13. Recharge the UPS for 8-16 hours to fully charge the battery.
REMINDER:
Batteries are considered HAZARDOUS WASTE and must be disposed of properly.
Most retailers that sell lead-acid batteries collect used batteries for recycling, as required by local
regulations.
TECHNICAL SPECIFICATIONS
Model
OM750ATLCD OM900ATLCD
OM1500ATLCD
Capacity (VA)
750VA
900VA
1500VA
Input
Voltage Range
82~148Vac
Frequency 50/60Hz(Auto
Sensing)
Output
On Battery Output
Voltage
Simulated Sine Wave at /-10%
On Battery Output
Frequency
50/60 Hz +/-1Hz
Overload Protection
Breaker/Internal Current Limiting
Physical
Outlets-total 6 8
Outlets-Battery &
Surge Protected
3 4
Outlets-SurgeOnly
Protected
3 4
Dimensions(W XH X
D)mm
96 X 138 X 286
148 X 178 X 298
Weight (kg)
4.0
4.9
9.3
Battery
Sealed Maintenance
Free Lead Acid
Battery
RBP0043X 1
RBP0110X 1
RBP0089X 2
Typical Recharge
Time
8 Hours
Warning Diagnostics
Indicators
Power On, UPS Status Display, Capacity Display, Digital Value Display
Audible Alarms
On Battery, Low Battery, Overload
Environmental
Operating
Temperature
0
C to 40
C
Operating Relative
Humidity
0 to 90%
Communication
PowerPanel
®
Personal Edition
Software
Windows 7/ Windows 8/Vista/XP/2000/Server 2003, Linux
Management
Auto-Charger Yes
Auto-Restart Yes
USB Yes
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
LCD Indication
Line mode
Select SW
Press
UPS Status Display
Capacity Display
Digital Value Display
Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
%
of Load
%
of Batt.
Initial
V X -- X V X V
1st
V X -- X V X V
2nd
V X -- X V X V
3rd
V
X
--
X
X
V V
4th
V
X
--
X
V
X
V
5th(Return) V X -- X V X V
Press >3sec
(Sound Disable)
V X V X -- -- -- -- -- -- --
Press >3sec
again
(Sound Enable)
V X X X -- -- -- -- -- -- --
(Overload) V X -- V -- -- -- -- -- -- --
“V” : Illuminated, “X” : Not Illuminated, “--“ : Either
Battery mode
Select SW
Press
UPS Status Display
Capacity Display
Digital Value Display
Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
%
of Load
%
of Batt.
Initial
X V -- X X V V
1st
X V -- X X V V
2nd
X V -- X V X V
3rd
X
V
--
X
X
V V
4th
X
V
--
X
X
V
V
5th(Return) X V -- X X V V
Press >3sec
(Sound Disable)
X V V X -- -- -- -- -- -- --
Press >3sec
again
(Sound Enable)
X V X X -- -- -- -- -- -- --
(Overload) X V -- V -- -- -- -- -- -- --
“V” : Illuminated, “X” : Not Illuminated, “--“ : Either
TROUBLE SHOOTING
Problem
Possible Cause
Solution
The UPS does
not perform
expected
runtime.
Batteries are not fully charged.
Recharge the battery by leaving the UPS
plugged in.
Battery is slightly worn out.
Contact CyberPower Systems Technical
Support.
The UPS will not
turn on.
The on/off switch is designed
to prevent damage by rapidly
turning it off and on.
Turn the UPS off. Wait 10 seconds and then
turn the UPS on.
The unit is not connected to an
AC outlet.
The unit must be connected to a
120V50/60Hz outlet.
The battery is worn out.
Contact CyberPower Systems Technical
Support.
Mechanical problem.
Contact CyberPower Systems Technical
Support.
Outlets do not
provide power to
equipment
Circuit breaker is tripped due
to overload
Turn the UPS off and unplug at least one
piece connected equipment. Unplug the
power cord of the UPS then press the circuit
breaker knob.
Batteries are discharged
Allow the unit to recharge for at least 4
hours.
Unit has been damaged by a
surge or spike.
Contact CyberPower Systems Technical
Support.
PowerPanel®
Personal Edition
is inactive
The serial/USB cable is not
connected.
Connect the serial/USB cable to the UPS
unit and an open serial port on the back of
the computer. You must use the cable that
came with the unit.
The unit is not providing
battery power.
Shutdown your computer and turn the UPS
off. Wait 10 seconds and turn the UPS back
on. This should reset the unit.
For more information, visit
www.cyberpower.com
All rights reserved. Reproduction without permission is prohibited.