Copyright © 2012 CyberPower Systems, Inc.
TECHNICAL SPECIFICATIONS
15
Model
CPSPV4000ETL
CPSPV5000ETL
Feature
Type of equipment
Grid tied PV inverter
Non-isolated (transformer-less)
Adjustable reactive power
Outdoor enclosure (IP65)
Input
Absolute maximum PV input
voltage
900 Vdc
Operation voltage range
250 ~ 900 Vdc
MPP voltage range @nominal
power
310 ~ 750 Vdc
Input power capture
>99%
Rating input voltage
650 Vdc
Inverter wake up voltage
< 200 Vdc (DC power supply on)
Start voltage
320 Vdc
MPPT tracker
1 tracker
Input current limitation
13.5 Adc
17 Adc
Max backfeed current
0 A
Maximum efficiency@650Vdc
97.6%
97.8%
European efficiency@650Vdc
97.0%
97.3%
Input protection
Voltage and current limitation
Array impedance measurement
Residual current measurement
Input detection tolerance
Input voltage deviation < 2%
Input current deviation <3%
Input power deviation <3%
Output
Output rating power
4000 Watt
5000 Watt
(For VDE-AR-N 4105: 4600 Watt )
Grid
Single phase
Grid rating voltage
230 Vac
Grid voltage range (Over /
under voltage disconnect)
180 ~ 270 Vac (According to code setting table)
Over / under voltage
disconnect time
According to code setting table
Grid rating current
17.4 A
21.7 A (20 A Germany)
Grid
maximum
continuous
current
20 A
24 A
Grid rating frequency
50 / 60 Hz
Grid maximum inrush current
<150 A
Maximum output fault current
>30A
Maximum output overcurrent
protection
40 A
50 A
Grid frequency range (Over /
under frequency disconnect)
50 / 60 +/- 5 Hz (According to code table setting)
Over / under frequency
disconnect time
According to code setting table
Active islanding method
Yes
Reconnect time (After grid
recover)
According to code setting table
Output current DC component
According to code setting table
Output current harmonic
distortion
< 5%
Adjustable reactive power
range
0.8 inductive ~0.8 capacitive
Nighttime power consumption
< 1 Watt
Output protection
Output AC fuse
Current limitation and thermal de-rating
Over temperature protection
Output detection tolerance
Utility voltage deviation < 1%