27
The control menu
:
By pressing , enter the menu of
"
Control
"
. The display would enter the next
control menu screen.
1) Buzzer mute
2) Battery test: is one command to control all UPS in a parallel system to do the
battery test at the same time.
3) Clear EPO status: once EPO status is enabled, the UPS output would be cut
off. To recover to normal status, first EPO connector should be closed, and
enter this menu to clear EPO status, then UPS would stop alarm and recover
to Bypass model. And UPS needs be turned on by manual operation.
4) Single UPS off: is one command to turn off one UPS which is operated
currently in parallel system, and other UPS continue working to supply the load
in the parallel system.
The setting menu
:
Please contact your local distributor for further information before using the settings.
Some settings would change the specification, and some settings would enable or
disable some functions. The unsuitable option set by user may result in potential
failures or protecting function loss, even directly damage the load, battery or
UPS.The most of settings could only be done while UPS is in Bypass mode.
Submenu item
Optional Values
Default Value
User password*
enabled/disabled
enabled
Audio alarm
enabled/disabled
enabled
Site wiring fault alarm
enabled/disabled
enabled
Ambient temperature warning
enabled/disabled
enabled
DC start
enabled/disabled
enabled
Auto Restart
enabled/disabled
enabled
Automatic overload restart
enabled/disabled
enabled
Auto Bypass
enabled/disabled
enabled