7
Frequency
Synchronized 50/60
×
(1
±
10%)Hz @Line mode
50/60
×
(1
±
0.1%)Hz @Battery mode
Wave Form
sine
Load Type
PF 0.5~1, lagging
THDV
≤
2% @ full linear load
;≤
5% @ full nonlinear load
Over Load**
Line mode:
10 min 105%~125%
1 min 125%~150%
10 s 150%~170%
100ms >170%
Battery mode:
2 min 105%
~
125%
30 s 125%
~
150%
100ms >150%
*The load capacity would be derated to 90% automatically when the output voltage
is adjusted to 208Vac.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
3.3. Operating Environment
Temperature
Humidity
Altitude
Storage
temperature
0
℃
~40
℃
<95%
<1000m
-15
℃
~50
℃
Note:
The load capacity should be derated 1% every 100m heightened on the basis
of 1000m.
3.4. Dimensions and Weights
Model
Dimensions
W×H×D(mm)
Net Weight(kg)
OLS6000ERT6U
438*261*680
72.5
OLS10000ERT6U
438*261*680
86
OLS6000ERT6UM
438*261*821
75.1
OLS10000ERT6UM
438*261*821
88.6