![CWSI WRA-3 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/cwsi/wra-3/wra-3_operating-and-installation-instruction-manual_2701256016.webp)
P/N IM-WRA-3 Rev. A
2012 Commercial Wireless Systems International, LLC.
16
Program device table screen
When programming is complete the lcd should display success as shown below. Remove the sd card
by pushing it in then release. The WRA-3 will initialize and send a power up reset trouble when it
connects to the network. All of the annunciators in the installation must be programmed.
Program successful screen
In the event the programming is not successful there will be a Failed Program message displayed
with a reason. The reasons are listed below with suggestions for correction. Follow the corrective
action and try programming again.
1. SD Card Invalid – Remove and replace SD card. Reformat the SD card. Try a new SD card.
2. Prog File Not Found – Verify the annunciator.bin file is on the SD card. Format the SD card
then rewrite the file again with the WRA-3 programmer.
3. Error Reading file - Verify the annunciator.bin file is on the SD card. Format the SD card
then rewrite the file again with the WRA-3 programmer. Try a new SD card.
Section 7 – Info and Maintenance
7.1 Menus
The info and maintenance menu provides general annunciator information such as software revision
level, serial number, base code as well as battery and charger voltage. It also has options for clearing
the base code and performing a signal survey. To enter the menu press turn the access key switch to
the access position then hold the ACK/STEP and SIGNAL SILENCE buttons simultaneously for 5
seconds. The WRA-3 will beep and light all of the leds. After entering menu mode the first screen will
show the software rev level of the annunciator. The different menu screens can now be selected by
pressing ACK/STEP button.
The menus are as follows:
1. Network Info – This screen shows the ID (serial number) of the annunciator as well as the
base code of the CP-3000A(DA) it is reporting to.
2. Signal Survey – This menu allows the installer to conduct a signal survey from the
annunciator. Refer to the signal survey section of this manual for instructions on conducting a signal
survey.
3. WRA-3 Voltages – This screen shows the latest voltage reading on the battery and battery
charger. The voltages are as read under load and displayed in millivolts. The readings are updated
Success
Remove SD to Reset
Program Device
Table?
Press Sil to Program