RESET – Resets the CP-3000A(DA), annunciator(s), active relays, nacs etc. to the normal condition.
Refer to the control panel manual for further information.
Section 5 – Operation
5.1 Overview
The WRA-3 annunciator is designed to be a display and control extension of the CP-3000A(DA)
control panel at up to 8 locations within the installation network. Control functions include
acknowledging, scrolling, signal silence and reset. The lcd display will show alarm, supervisory and
trouble signals with the highest priority signal displayed. Each annunciator is independently monitored
for troubles including signal integrity, programming, power supply, charger, tamper etc. A complete
list of trouble signals is included in this section. The annunciator is programmed by inserting a
standard sd card which has been programmed with the panel information via the WRA-3 programmer
software.
5.2 Normal standby
When the installation has no off normal conditions the annunciator will display the system normal
screen shown below. The system time shown on the CP-3000A(DA) is also shown on the annunciator
in 24 hour format.
5.3 Alarm, Supervisory and Trouble annunciation
When an alarm is received:
1. The Alarm led will flash.
2. The sounder turns on steady.
3. The lcd shows the alarm level, device type, description, serial number and number of events
in process.
4. Press ACK/STEP to acknowledge active events. Flashing leds turn on steady and sounder
silences
5. Press SIGNAL SILENCE to silence any active nac’s if programmed.
6. Press RESET to reset the system back to normal standby.
Typical alarm screen
When a supervisory is received:
1. The Supervisory led will flash.
Alarm A 1/8
Pull Station 4003cb
West Stairwell
CWSI
System Normal
CP3000A
14:30