TITLE:
General Specification: Lightning Protection and Grounding
Rev -, ECN 027194
LIGHTING PROTECTION AND GROUNDING
Read all of Section B and this section before attempting any procedure. Pay particular attention to all Notes, Cautions and Warnings
9. Lightning Protection System
The lightning protection system provides a non-destructive path to ground for lightning energy contacting or induced
onto or in a building. To effectively protect from lightning damage, air terminals are installed according to the National
Fire Protection Association Lightning Protection Code (NFPA 780). Air terminals will intercept the discharge to keep it
from penetrating or structurally damaging the building. This is done by providing a low impedance path from the air ter-
minals to the earth electrode system.
10. Equipment Fault and Personal Safety System
The equipment fault protective system ensures that personnel are protected from shock hazard and equipment is pro-
tected from damage or destruction resulting from faults (lightning induced surges) that may develop in the electrical sys-
tem. Deliberately engineered ground conductors (green wire safety ground) shall be provided throughout the AC
distribution system to afford electrical paths of sufficient capacity, so that protective devices can operate promptly and
efficiently. The use of conduit for grounding in lieu of a dedicated green wire is unacceptable.
Install the green wire ground (#6 stranded) with the AC power distribution conductors. There shall be no green wires
spliced within the conduit. All splices shall be performed at the appropriate junction boxes.
Bond the ground conductor to all pull boxes, junction boxes and power panels.
In existing facilities where an existing conduit is not large enough to accommodate an additional ground conductor, or
where a conduit section is insulated from other conduit sections, an external ground conductor may be installed to main-
tain continuity. All mounting hardware and connectors shall be UL approved.
All DC chargers are to be grounded to the green wire ground using UL approved connectors. At no point should the
chargers be isolated from the grounding system.
All interior grounding should return to a single ground point. From this location it is then connected to the exterior ground
system. Optional Interior Ground Halo: If an interior ground halo is to be installed around the inside perimeter of the
structure, this conductor (#2/0 green insulated minimum) shall be securely fastened to the structure.
All connections to the halo shall be made using UL listed connectors.
Transient Voltage Surge Suppression: TVSS shall be provided at the main electrical service entrance panel. Protection
at this point shall be as follows:
UL 1449 Listed device
25,000 ampere surge capacity with maximum 495 volt clamping voltage
Protection should be Line to Ground, Neutral to Ground and Line to Neutral
Internally fused for safety
Failure mode indicator lights
Suppression may be as the 14000 series of Harger Lightning Protection, Inc., 1066 Campus Drive, Mundelein, IL (800-
842-7437), or MBP 120EFI series from EFI Electronics Corporation, 2415 South 2300 West, Salt Lake City, UT (801-
977-9009).
Содержание MINUTE MISER
Страница 7: ...Page iv Repair and Service Manual TABLE OF CONTENTS Notes...
Страница 11: ...Owner s Manual and Service Guide SAFETY INFORMATION Page viii Notes...
Страница 27: ...SAFETY Page B ii Repair and Service Manual Notes...
Страница 37: ...BODY Page C ii Repair and Service Manual Notes...
Страница 41: ...WHEELS AND TIRES Page D ii Repair and Service Manual Notes...
Страница 45: ...BATTERIES AND CHARGING Page E ii Repair and Service Manual Notes...
Страница 55: ...ELECTRONIC SPEED CONTROL Page F ii Repair and Service Manual Notes...
Страница 61: ...MOTOR Page G ii Repair and Service Manual Notes...
Страница 67: ...ELECTRICAL SYSTEM AND BATTERY CHARGER Page H ii Repair and Service Manual Notes...
Страница 81: ...Page J ii BRAKES Repair and Service Manual Notes...
Страница 87: ...BRAKES Page J 6 Repair and Service Manual Notes...
Страница 89: ...REAR AXLE Page K ii Repair and Service Manual Notes...
Страница 95: ...PAINT Page L ii Repair and Service Manual Notes...
Страница 99: ...LIGHTNING PROTECTION AND GROUNDING Page M ii Repair and Service Manual Notes...
Страница 105: ...GENERAL SPECIFICATIONS Page N ii Repair and Service Manual Notes...
Страница 109: ...Page N 4 Repair and Service Manual GENERAL SPECIFICATIONS Notes...
Страница 111: ...STEERING Page P ii Repair and Service Manual Notes...